19.3
IEC/UCA 61850-9-2LE communication protocol
SEMOD172279 v3
19.3.1
Introduction
SEMOD166571-1 v2
SEMOD166590-5 v6
Every IED can be provided with communication interfaces enabling it to connect to
the process buses in order to get data from analog data acquisition units close to the
process (primary apparatus), commonly known as Merging Units (MU). The
protocol used in this case is the IEC/UCA 61850-9-2LE communication protocol.
The IEC/UCA 61850-9-2LE standard does not specify the quality of the sampled
values. Thus, the accuracy of the current and voltage inputs to the merging unit and
the inaccuracy added by the merging unit must be coordinated with the requirement
for the actual type of protection function.
Factors influencing the accuracy of the sampled values from the merging unit are,
for example, anti aliasing filters, frequency range, step response, truncating, A/D
conversion inaccuracy, time tagging accuracy etc.
In principle, the accuracy of the current and voltage transformers, together with the
merging unit, will have the same quality as the direct input of currents and
voltages.
The process bus physical layout can be arranged in several ways, described in
Annex B of the standard, depending on what are the needs for sampled data in a
substation.
1MRK 511 407-UEN C
Section 19
Station communication
Phasor measurement unit RES670 2.2 IEC
295
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...