5.4
Local HMI functionality
5.4.1
Protection and alarm indication
GUID-09CCB9F1-9B27-4C12-B253-FBE95EA537F5 v17
Protection indicators
The protection indicator LEDs are Ready, Start and Trip.
The yellow and red status LEDs are configured in the disturbance
recorder function, DRPRDRE, by connecting a start or trip signal
from the actual function to a BxRBDR binary input function block
using the PCM600 and configure the setting to
Off
,
Start
or
Trip
for
that particular signal.
Table 7:
Ready LED (green)
LED state
Description
Off
Auxiliary supply voltage is disconnected.
On
Normal operation.
Flashing
Internal fault has occurred.
Table 8:
Start LED (yellow)
LED state
Description
Off
Normal operation.
On
A protection function has started and an indication message is displayed.
The start indication is latching and must be reset via communication,
LHMI or binary input on the LEDGEN component. To open the reset
menu on the LHMI, press
.
Flashing
The IED is in test mode and protection functions are blocked, or the
IEC61850 protocol is blocking one or more functions.
The indication disappears when the IED is no longer in test mode and
blocking is removed. The blocking of functions through the IEC61850
protocol can be reset in Main menu/Test/Reset IEC61850 Mod. The
yellow LED changes to either On or Off state depending on the state of
operation.
1MRK 511 407-UEN C
Section 5
Local HMI
Phasor measurement unit RES670 2.2 IEC
83
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...