6.2
View analog primary values
6.2.1
Overview
The analog primary values are analog quantities measured on the primary side of
the TRM and reflect the actual current or voltage on the primary side of the CTs.
The ratio is adjusted under settings and also depends on the rating of the TRM. 24
primary values and phase angles are displayed in this view.
6.3
View analog secondary values
6.4
View analog mean values
6.4.1
Overview
Measurements from the Milliampere Input Module (MIM) are found in this part of
the measurements menu. Data from either the hard wired mA module or Signal
Matrix Tool mA modules are shown here.
6.4.1.1
mA input module MIM
Main menu/Measurements/Analog mean values/mA modules/MIM:x
Displays input data from the milli-ampere module which has six inputs. Each input
has a range of +/- 20 mA. The value displayed on the screen is however dependant
on the settings for the Milli-ampere Module. In the menu for settings, the range and
a transformation factor can be adjusted to suit the application. This means that an
input 3 mA may be displayed as temperature of 45 degrees. The output values
shown are without units.
6.5
View monitoring values
6.5.1
Service values CVMMXN
Main menu/Measurement/Monitoring/ServiceValues(MMXN)/CVMMXN:x
Displays up to three instances of CVMMXN with measured values for S, P, Q, PF,
U, I, ILead, ILag and F.
Section 6
1MRK511251-UEN B
Read measured values
28
Operator's manual
Summary of Contents for Relion RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 Operator s manual...
Page 2: ......
Page 13: ...Section 15 Glossary 79 Table of contents 7 Operator s manual...
Page 14: ...8...
Page 20: ...14...
Page 24: ...18...
Page 32: ...26...
Page 38: ...32...
Page 72: ...66...
Page 76: ...70...
Page 84: ...78...
Page 93: ...87...