15.8.1.3
Technical data
GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1
Table 294:
Number of ANDQT instances
Logic block
Quantity with cycle time
3 ms
8 ms
100 ms
ANDQT
-
20
100
15.8.2
Single point indication related signals combining function
block INDCOMBSPQT
GUID-13C9325D-D3A0-480F-9F3B-738A13E0ECF8 v3
GUID-EEBD65A5-394C-4ECD-BF6F-D556B610FC57 v3
The value of single point input (SP_IN) is copied to the value part of the SP_OUT
output. The TIME input is copied to the time part of the SP_OUT output. State input
bits are copied to the corresponding state part of the SP_OUT output. If the state or
value on the SP_OUT output changes, the Event bit in the state part is toggled.
INDCOMBSPQT can propagate the quality, the value and the time stamps of the
signals via IEC 61850.
15.8.2.1
Function block
GUID-55B49FC7-8239-4891-BE16-29296A8F40BE v1
INDCOMBSPQT
SP_IN*
TIME*
BLOCKED*
SUBST*
INVALID*
TEST*
SP_OUT
IEC15000146.vsd
IEC15000146 V1 EN-US
Figure 170:
INDCOMBSPQT function block
15.8.2.2
Signals
GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1
PID-3792-INPUTSIGNALS v2
Table 295:
INDCOMBSPQT Input signals
Name
Type
Default
Description
SP_IN
BOOLEAN
0
Single point indication
TIME
GROUP
SIGNAL
0
Timestamp
BLOCKED
BOOLEAN
0
Blocked for update
SUBST
BOOLEAN
0
Substituted
INVALID
BOOLEAN
0
Invalid value
TEST
BOOLEAN
0
Testmode
Section 15
1MRK 511 408-UUS A
Logic
446
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...