Name
Type
Default
Description
RSTCBWR
BOOLEAN
0
Reset of CB remaining life and operation counter
RSTTRVT
BOOLEAN
0
Reset of CB closing and opening travel times
RSTIPOW
BOOLEAN
0
Reset of accumulated I^CurrExponent
RSTSPCHT
BOOLEAN
0
Reset of CB spring charging time
PID-3267-OUTPUTSIGNALS v10
Table 410:
SSCBR Output signals
Name
Type
Description
OPENPOS
BOOLEAN
CB is in open position
CLOSEPOS
BOOLEAN
CB is in closed position
INVDPOS
BOOLEAN
CB is in Invalid Position
TRCMD
BOOLEAN
Open command issued to CB
TRVTOPAL
BOOLEAN
CB open travel time exceeded set value
TRVTCLAL
BOOLEAN
CB close travel time exceeded set value
OPERALM
BOOLEAN
Number of CB operations exceeds alarm limit
OPERLO
BOOLEAN
Number of CB operations exceeds lockout limit
CBLIFEAL
BOOLEAN
Remaining life of CB reduced to Life alarm level
MONALM
BOOLEAN
CB 'not operated for long time' alarm
IPOWALPH
BOOLEAN
Accum I^CurrExponent integr over CB open travel
time exceeds alarm limit
IPOWLOPH
BOOLEAN
Accum I^CurrExponent integr over CB open travel
time exceeds lockout limit
SPCHALM
BOOLEAN
Spring charging time has crossed the set value
GPRESALM
BOOLEAN
Pressure below alarm level
GPRESLO
BOOLEAN
Pressure below lockout level
16.4.5
Settings
PID-3267-SETTINGS v10
Table 411:
SSCBR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
PhSel
Phase A
Phase B
Phase C
-
-
Phase A
Phase selection
Table continues on next page
Section 16
1MRK 511 408-UUS A
Monitoring
534
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...