16.4.7.2
Circuit breaker status
GUID-390A1250-B258-4023-9A7D-0D7E19E13A6C v12
The circuit breaker status subfunction monitors the position of the circuit breaker, that
is, whether the breaker is in the open, closed or error position. The operation is
described in figure
Phase current
check
Contact
position
indicator
POSCLOSE
POSOPEN
I3P-ILRMSPH
OPENPOS
CLOSEPOS
INVDPOS
IEC12000613-3-en.vsd
IEC12000613 V3 EN-US
Figure 210:
Functional module diagram for monitoring circuit breaker status
Phase current check
The module compares the phase current I3P-ILRMSPH to the
AccStopCurr
setting. If
the current in the selected phase exceeds the set level, it is reported to the contact
position indicator module as closed circuit breaker.
Contact position indicator
The circuit breaker status is open when the auxiliary input contact
POSCLOSE
is low,
the
POSOPEN
input is high and the phase current is less than the setting
AccStopCurr
value. The circuit breaker is closed when the
POSOPEN
input is low and the
POSCLOSE
input is high. The breaker is in the error state if both auxiliary contacts
have the same value or if the auxiliary input contact
POSCLOSE
is low and the
POSOPEN
input is high but the current is above the setting
AccStopCurr
.
The status of the breaker is indicated with the binary outputs
OPENPOS
,
CLOSEPOS
and
INVDPOS
for open, closed and error position respectively.
16.4.7.3
Remaining life of circuit breaker
GUID-C347406A-2B6F-42BD-B70B-51489AB51EAE v12
The Remaining life of circuit breaker subfunction is used to give an indication on the
wear and tear of the circuit breaker. Every time the breaker operates, the life of the
circuit breaker reduces due to wear. The breaker wear depends on the interrupted
current. The remaining life of the breaker is estimated from the circuit breaker trip
curve provided by the manufacturer. The remaining life is decreased by at least one
when the circuit breaker is opened. The operation of the remaining life of circuit
breaker subfunction is described in figure
Section 16
1MRK 511 408-UUS A
Monitoring
540
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...