Section 3
Analog inputs
SEMOD55010-1 v3
3.1
Introduction
SEMOD55003-5 v11
Analog input channels must be configured and set properly in order to get correct
measurement results and correct protection operations. For power measuring, all
directional and differential functions, the directions of the input currents must be
defined in order to reflect the way the current transformers are installed/connected in
the field ( primary and secondary connections ). Measuring and protection algorithms
in the IED use primary system quantities. Setting values are in primary quantities as
well and it is important to set the data about the connected current and voltage
transformers properly.
An AISVBAS reference
PhaseAngleRef
can be defined to facilitate service values
reading. This analog channel's phase angle will always be fixed to zero degrees and
remaining analog channel's phase angle information will be shown in relation to this
analog input. During testing and commissioning of the IED, the reference channel can
be changed to facilitate testing and service values reading.
The IED has the ability to receive analog values from primary
equipment, that are sampled by Merging units (MU) connected to a
process bus, via the IEC 61850-9-2 LE protocol.
The availability of VT inputs depends on the ordered transformer input
module (TRM) type.
3.2
Function block
SEMOD116577-1 v5
The hardware channels appear in the signal matrix tool (SMT) and in
ACT when a TRM is included in the configuration with the hardware
configuration tool. In the SMT or the ACT, they can be mapped to the
1MRK 511 408-UUS A
Section 3
Analog inputs
Phasor measurement unit RES670 2.2 ANSI
57
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...