5.4
Local HMI functionality
5.4.1
Protection and alarm indication
GUID-09CCB9F1-9B27-4C12-B253-FBE95EA537F5 v15
Protection indicators
The protection indicator LEDs are Normal, Pickup and Trip.
Table 10:
Normal LED (green)
LED state
Description
Off
Auxiliary supply voltage is disconnected.
On
Normal operation.
Flashing
Internal fault has occurred.
Table 11:
PickUp LED (yellow)
LED state
Description
Off
Normal operation.
On
A protection function has picked up and an indication message is displayed.
The pick up indication is latching and must be reset via communication,
LHMI or binary input on the LEDGEN component. To open the reset menu
on the LHMI, press
.
Flashing
The IED is in test mode and protection functions are blocked, or the
IEC61850 protocol is blocking one or more functions.
The indication disappears when the IED is no longer in test mode and
blocking is removed. The blocking of functions through the IEC61850
protocol can be reset in Main menu/Test/Reset IEC61850 Mod. The yellow
LED changes to either On or Off state depending on the state of operation.
Section 5
1MRK 504 163-UUS A
Local HMI
106
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...