X
0E
X
0
X
m0
+
=
EQUATION554 V1 EN-US
(Equation 85)
Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1
0
m
f
Z
K
Z
Z
R
= -
×
+
+
EQUATION1426 V1 EN-US
(Equation 86)
If the denominator in equation
is called B and Z0m is simplified to X0m, then the
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
( )
( )
( )
( )
2
2
0
Re
Re
0
1
Re
Im
X m
B
K
B
B
×
= -
+
EQUATION1427 V2 EN-US
(Equation 87)
( )
( )
( )
( )
2
2
0
Im
Im
0
Re
Im
X m
B
K
B
B
×
=
+
EQUATION1428 V2 EN-US
(Equation 88)
Parallel line is out of service and grounded in both ends
SEMOD168247-69 v2
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-ground-faults. Set the values of the corresponding zone (zero-
sequence resistance and reactance) equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
+
è
ø
ç
÷
æ
ö
×
=
EQUATION561 V1 EN-US
(Equation 89)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
–
è
ø
ç
÷
æ
ö
×
=
EQUATION562 V1 EN-US
(Equation 90)
Section 8
1MRK 504 163-UUS A
Impedance protection
244
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...