ANSI11000304-1-en.vsd
ANSI11000304 V1 EN-US
Figure 254:
Load Encroachment characteristic in under Impedance function
The resistive settings of this function is also provided in percentage of
ZBase
.
It is calculated according to equation
(
/ 3) /
ZBase
VRated
IRated
=
GUID-90239033-D824-4479-A03A-41EE034C9021-ANSI V1 EN-US
(Equation 412)
The
LdAngle
is a separate setting.
8.21.2.8
External block signals
GUID-8DDEDD52-37DC-4330-BE56-CBC37F0545AD v2
The under impedance function will have to be blocked in the event of PT fuse fail. A
BLKZ input for this purpose is provided. Also a BLOCK input is provided.
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
507