voltage and angle values and a time stamp. The fault recording
can be triggered by the start or the trip signal of a protection
block, or by both. The available measurement modes include
DFT, RMS and peak-to-peak. Fault records store relay
measurement values at the moment when any protection
function starts. In addition, the maximum demand current with
time stamp is separately recorded. The records are stored in
the non-volatile memory.
1024
PROCESS LEVEL
USER LEVEL
Fault summary;
Trip timestamp, Function, Currents, Voltages, etc.
BAS
IC
FUNC
TI
O
NS
IE
C
6185
0-
8-
1
Modbu
s
IE
C
10
3
DN
P3
LH
M
I
W
H
M
I
PC
M60
0
Process
events
(FIFO)
128
Fault
records
(FIFO)
System and security-related events;
Configuration changes, Control, Login, etc.
2048
Audit
trail
events
(FIFO)
n…100
Disturbance
records
...7 yrs
Load profile
record
Historical load data captured at a periodical
time interval (Demand interval 1 ...180min)
Function specific data
Min/max demand currents, Operation counters, etc.
History view
GUID-CDF1DC16-AF90-406F-B21B-EF6C7F60BCCA V1 EN
Figure 8.
Recording and event capabilities overview
12. Condition monitoring
The condition monitoring functions of the relay constantly
monitor the performance and the condition of the circuit
breaker. The monitoring comprises the spring charging time,
SF6 gas pressure, the travel time and the inactivity time of the
circuit breaker.
The monitoring functions provide operational circuit breaker
history data, which can be used for scheduling preventive
circuit breaker maintenance.
In addition, the relay includes a runtime counter for monitoring
of how many hours a protected device has been in operation
thus enabling scheduling of time-based preventive
maintenance of the device.
13. Trip-circuit supervision
The trip-circuit supervision continuously monitors the
availability and operability of the trip circuit. It provides open-
circuit monitoring both when the circuit breaker is in its closed
and in its open position. It also detects loss of circuit-breaker
control voltage.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
13