22. Mounting methods
By means of appropriate mounting accessories, the standard
relay case can be flush mounted, semi-flush mounted or wall
mounted. The flush mounted and wall mounted relay cases can
also be mounted in a tilted position (25°) using special
accessories.
Further, the relays can be mounted in any standard 19”
instrument cabinet by means of 19” mounting panels available
with cut-outs for one or two relays.Alternatively, the relays can
be mounted in 19” instrument cabinets by means of 4U
Combiflex equipment frames.
For routine testing purposes, the relay cases can be equipped
with test switches, type RTXP 18, which can be mounted side
by side with the relay cases.
Mounting methods
• Flush mounting
• Semi-flush mounting
• Semi-flush mounting in a 25° tilt
• Rack mounting
• Wall mounting
• Mounting to a 19" equipment frame
• Mounting with an RTXP 18 test switch to a 19" rack
Panel cut-out for flush mounting
• Height: 161.5 ±1 mm
• Width: 165.5 ±1 mm
48
17
7
16
0
177
153
164
IECA070900 V4 EN
Figure 14.
Flush mounting
98
17
7
16
0
186
103
IECA070903 V4 EN
Figure 15.
Semi-flush mounting
23
0
107
25°
133
190
IECA070902 V4 EN
Figure 16.
Semi-flush mounting in a 25º tilt
23. Relay case and plug-in unit
The relay cases are assigned to a certain type of plug-in unit.
For safety reasons, the relay cases for current measuring relays
are provided with automatically operating contacts for short-
circuiting the CT secondary circuits when a relay unit is
withdrawn from its case. The relay case is further provided with
a mechanical coding system preventing the current measuring
relay units from being inserted into relay cases intended for
voltage measuring relay units.
24. Selection and ordering data
to access the selection and ordering
information and to generate the order number.
(PST), a Next-Generation Order Number
Tool, supports order code creation for ABB Distribution
Automation IEC products with emphasis on, but not exclusively
for, the Relion product family. PST is an easy-to-use, online tool
always containing the latest product information. The complete
order code can be created with detailed specification and the
result can be printed and mailed. Registration is required.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
47
Summary of Contents for RELION REV615
Page 1: ... RELION 615 SERIES Capacitor Bank Protection and Control REV615 Product Guide ...
Page 58: ...58 ...
Page 59: ......