background image

5.  Application

CONDITION MONITORING 
AND SUPERVISION

1 0 1 0 0 0 1 1 0 0 1 1 0 0

1 0 1 1 0 0 1 0 1 1 1 0 0 1 0

1 1 0 0 1 1 1 0 1 1 0 1 0

1 0 1 1 0 1 1 0 1 1 0 1 0 0

1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 0 0 1 1 0 0

1 0 1 1 0 0 1 0 1 1 1 0 0 1 0

1 1 0 0 1 1 1 0 1 1 0 1 0

1 0 1 1 0 1 1 0 1 1 0 1 0 0

OR

AND

PROTECTION AND CONTROL RELAY
Example of a combination of application packages for feeder protection 

PROTECTION

LOCAL HMI (OPTIONAL)

REX640

REMARKS

Total nr. of instances

One instance available, common for 
Line Distance (APP3) and Line 
Differential (APP4) application 
packages

APPLICATION PACKAGE FOR FEEDER EF PROTECTION EXTENSION

APPLICATION PACKAGE FOR FEEDER FAULT LOCATOR

APPLICATION PACKAGE FOR LINE DISTANCE PROTECTION

APPLICATION PACKAGE FOR LINE DIFFERENTIAL PROTECTION

APP3 / APP4

ALSO AVAILABLE

- Disturbance and fault recorders
- Sequence event recorder
- Relay self-supervision
- User management and logging
- Logical and mathematical functions
- WebHMI
  

Ctrl 

1)

Ind 

2)

COMMUNICATION

Protocols:

 

IEC 61850-8-1/-9-2LE

 Modbus

®

 

IEC 60870-5-103

 DNP3

Interfaces:

 

Ethernet:  TX (RJ45), FX (LC)

 Serial: 

Serial glass fiber (ST),  

  

RS-485

Redundant protocols:

 HSR
 PRP

Time synchronization:

 SNTP
 PTPv2
 IRIG-B

LOADPROF
LOADPROF

PQM3IH

PQM ITHD, IDC

PQM3VH

PQM VTHD, VDC

PQUUB

PQMV UB

PQMU

PQMV SWE,SAG,

INT

- 7-inch color touch screen
- Ready-made pages and 
  customizable pages
- Increased situational awareness 
  towards process
- Supports Relay testing and 
  commissioning
- Graphical editing of pages with 
  PCM600 tool

Master Trip

94/86

MEASUREMENT

- I, U, Io, Uo, P, Q, E, pf, f
- Sequence current/voltage measurement
- Limit value supervision
- RTD/mA measurement and mA output 

Analog interface types

AIM1

Current transformer

5

1)

Voltage transformer

5

1)

 One of available current transformer 

inputs is sensitive (0.2/1 A)

CLCRWN

85 67G/N CREV,WEI

CLN

85 67G/N SCHLGC

CLCRW

85 21CREV,WEI

Io>

IEF

67NTEF/NIEF

I2

→,

Io

67N-TC

Yo>

21NY

Io>

→Y

67NYH

Po>

32N

Io>HA

51NH

HIF
HIZ

FLOC
FLOC

CL

85 21SCHLGC

CLCRW

85CRW

LAL

21LAL

Φ

 <

78PS

BST
BST

Z<

21P,21N

CONTROL AND INDICATION

 

Object

CB

-

DC, 3 state

DC

 

 

 

 

 

 

8

6

ES

3

Control and status indication function for 
primary object
Status indication function for primary 
object   

1)

2)

3

8

6

3

PCS
PCS

A)

A)

3Id/I> 

87L

BST
BST

B)

B)

Two instances available, common 
for Line Distance (APP3) and Line 
Differential (APP4) application 
packages

B)

O

I

79

25AU-

TOSYNC

SYNC

25

CVPSOF 

SOFT

Io>>

67G/N-2 
51G/N-2

3I>

67P/

51P-1

ARC
AFD

MAP
MAP

24×

I2/I1>

46PD

3Ith>F

49F

3U<

27

UFLS/R

81LSH

Io>>>

50G/50N

f>/f<,df/dt

81

12×

Uo>

59G/59N

U2>

59NS

U1>

59PS

U1<

27PS

3I>>>

50P

3I>/Io>BF

50BF

3I>

51P-1

3I>>

51P-2

3I(U)

51V

3I>>

67P/

51P-2 

dIoHi>

87NHI 

dIoLo>

87NLI

I2>

67Q

3U<R

27R

Io>

67G/N-1 
51G/N-1

I2>M

46M

Io>>

51G/

51N-2

3I2f>

68HB 

3I<

37

3U>

59

Io>

51G/

51N-1

CBCM

52CM

FUSEF

VCM, 60

MCS 3I

CCM

TCS

TCM

OPTS

OPTM

3I

Io

3U

U

Uo

APP1

APP3

APP4

APP2

GUID-71448271-EE0E-4E5B-BCB6-671CEB238139 V2 EN

Figure 7.

Feeder application

Figure 7

 presents REX640 in a feeder application. The base

functionality is enhanced with application packages providing
both line distance and line differential protections. To provide

additional protection against earth faults along the feeder, an
additional application package has been selected.
Conventional measuring transformers are used in the example

1MRS759144 A

REX640

 

Product version: 1

 
 

10

ABB

Summary of Contents for RELION REX640

Page 1: ...RELION PROTECTION AND CONTROL REX640 Product Guide...

Page 2: ...4 Selection and ordering data 100 25 Modification Sales 100 26 Accessories and ordering data 101 27 Tools 102 28 Module diagrams 104 29 Certificates 113 30 References 113 31 Functions codes and symbol...

Page 3: ...gle REX640 relay For the selected application packages the functionality can be extended by including the related add on package The REX640 connectivity package guides the engineer in optimizing the a...

Page 4: ...Slot E Slot F Slot G ARC1001 o COM1001 COM1002 COM1003 COM1004 COM1005 BIO1001 o o BIO1002 o o BIO1003 o BIO1004 o RTD1001 o o AIM1001 o AIM1002 o SIM1001 o PSM1001 PSM1002 PSM1003 Mandatory to have...

Page 5: ...UID 5D4C7B10 17CA 4F59 B9E0 8024CB82CDE8 V1 EN Figure 2 Hardware module slot overview of the REX640 relay 1 Slot markings in enclosure top and bottom 2 Ready LED 1MRS759144 A REX640 Product version 1...

Page 6: ...6 CT 4 VT SIM1001 3 combi sensor inputs 1 CT sensitive for residual current only 1 VT PSM1001 24 60 VDC 3 PO TCS 2 PO 3 SO 2 SSO PSM1002 48 250 VDC 100 240 VAC 3 PO TCS 2 PO 3 SO 2 SSO PSM1003 110 125...

Page 7: ...n the local HMI The Home button at the bottom of the LHMI indicates the relay s status at a glance In normal situations the Home button shows a steady green light Any other situation that requires the...

Page 8: ...he LHMI can be connected to the relay also via station communication network if a longer distance is required between the relay and the LHMI Additionally the LHMI contains one Ethernet service port wi...

Page 9: ...D 1 2 GUID D53AE6BA 8746 4796 B1C9 13352190FAEA V1 EN Figure 6 LHMI connectors 1 USB port 2 RJ 45 ports 1MRS759144 A REX640 Product version 1 ABB 9...

Page 10: ...measurement Limit value supervision RTD mA measurement and mA output Analog interface types AIM1 Current transformer 51 Voltage transformer 5 1 One of available current transformer inputs is sensitive...

Page 11: ...rrent voltage measurement Limit value supervision RTD mA measurement and mA output 3Ith T G C 49T G C MCS 3I I2 CCM 3I I2 OLGAPC OLGAPC 3dI 3W 87T3 3dI T 87T COLTC 90V TPOSM 84T 5 3U LOADPROF LOADPROF...

Page 12: ...ool Master Trip 94 86 MEASUREMENT I U Io Uo P Q E pf f Sequence current voltage measurement Limit value supervision RTD mA measurement and mA output Analog interface types AIM1 AIM2 RTD1 Current trans...

Page 13: ...ation of two alternating power sources can be done by matching their voltage frequency phase sequence and phase angle The circuit breaker CB connects the two sources after a period of CB closing time...

Page 14: ...x 3x 3x 3x 3x 3x GUID E302427A 35A5 4CA0 AAED 75308A388E23 V1 EN Figure 11 Busbar protection application Figure 11 presents REX640 in a phase dedicated high impedance busbar protection application for...

Page 15: ...ed with arc flash sensor card The card supports a maximum of four pieces of either loop or lens sensors or a combination thereof By using suitable sensor combinations for different bays we can build u...

Page 16: ...indication function for primary object Status indication function for primary object 1 2 3 8 6 3 LOADPROF LOADPROF PQM3IH PQM ITHD IDC PQM3VH PQM VTHD VDC PQUUB PQMV UB 2 PQMU PQMV SWE SAG INT 2 CVPS...

Page 17: ...PP10 Transf AVR 3U 3U 3I 3U REX640 SIM1 1CT 1VT 3 combi sensors Base Functionality LHMI 3U Io Io GUID 4205F769 320E 42B1 8206 1F266F73D4FC V1 EN Figure 14 Digital switchgear application REX640 is perf...

Page 18: ...the substation level functionality COM600S features a Web browser based HMI which provides a customizable graphical display for visualizing single line mimic diagrams for switchgear bay solutions The...

Page 19: ...horizontal GOOSE communication IEC 61850 PCM600 Ethernet switch COM600S Web HMI Analog and binary horizontal GOOSE communication IEC 61850 GUID 16386136 ADEF 4835 9177 D8B6650E05CB V2 EN Figure 15 ABB...

Page 20: ...riable length The synchronizer function block has three different function modes manual semi automatic and automatic In each of these modes the LHMI acts as the local user interface The LHMI includes...

Page 21: ...service that utilities can provide for their industrial and key customers A monitoring system can provide information about system disturbances and their possible causes It can also detect problem co...

Page 22: ...events The records can be used to analyze the power system events Each record includes for example current voltage and angle values and a time stamp The fault recording can be triggered by the start...

Page 23: ...SDM600 or an Active Directory AD server such as Windows AD The relay supports full Public Key Infrastructure as defined by IEC 62351 9 With this the user can ensure that the certificates used in secu...

Page 24: ...d to the Ethernet based IEC 61850 Modbus and DNP3 protocols The IEC 61850 standard specifies network redundancy which improves the system availability for the substation communication The network redu...

Page 25: ...records If a Modbus TCP connection is used five clients can be connected to the relay simultaneously Further Modbus serial and Modbus TCP can be used in parallel and if required both IEC 61850 and Mod...

Page 26: ...nnel 1310 nm multimode or single mode fibers with LC connectors are used The communication link transfers analog and binary information between line ends for line differential line distance and transf...

Page 27: ...ferential protection function can be blocked if severe interference in the communication link risking the correct operation of the function is detected If the interference persists an alarm signal is...

Page 28: ...240 V AC 50 and 60 Hz 110 125 V DC 48 60 110 125 220 250 V DC Maximum interruption time in the auxiliary DC voltage without resetting the relay 50 ms at Un Auxiliary voltage variation 50 120 of Un 12...

Page 29: ...l withstand capability Continuously 4 A 20 A For 1 s 100 A 500 A Dynamic current withstand Half wave value 250 A 1250 A Input impedance 100 m 20 m Voltage inputs Rated voltage 57 240 V AC Voltage with...

Page 30: ...t 100 per lead Isolation 2 kV inputs to protective earth Response time 1 s RTD resistance sensing current 1 mA rms Operation accuracy Resistance Temperature 2 0 or 1 1 C mA inputs Supported current ra...

Page 31: ...en the control circuit time constant L R 40 ms at 110 V DC 0 25 A Minimum load current 1 mA Maximum operation frequency at 50 duty cycle 10 Hz Table 17 Double pole power output relays with TCS functio...

Page 32: ...ear interface Type Counter connector Serial port X8 10 pin 2 row counter connector Serial port X7 Optical ST connector Table 20 USB interface LHMI Type Description USB Hi Speed USB Type A Table 21 Eth...

Page 33: ...mm Table 25 Degree of protection of flush mounted protection relay Description Value Front connector side IP 20 Top and bottom IP 30 Rear IP 40 Table 26 Degree of protection of the LHMI Description Va...

Page 34: ...MHz IEC 61000 4 3 IEC 60255 26 class III 10 V m f 900 MHz ENV 50204 IEC 60255 26 class III 20 V m rms f 80 1000 MHz IEEE C37 90 2 2004 Fast transient disturbance test IEC 61000 4 4 IEC 60255 26 IEEE...

Page 35: ...m distance 230 1000 MHz 47 dB V m quasi peak measured at 10 m distance 1 3 GHz 76 dB V m peak 56 dB V m average measured at 3 m distance 3 6 GHz 80 dB V m peak 60 dB V m average measured at 3 m distan...

Page 36: ...2 1 Damp heat test 6 cycles 12 h 12 h at 25 C 55 C humidity 93 IEC 60068 2 30 Change of temperature test 5 cycles 3 h 3 h at 25 C 55 C IEC60068 2 14 Storage test 96 h at 40 C 96 h at 85 C IEC 60068 2...

Page 37: ...e set value or 0 002 Un Impedance 2 5 of the set value or 0 05 Phase angle 2 Shortest operate time1 SIR2 0 1 50 25 ms Transient overreach SIR 0 1 50 8 5 Reset time Typically 45 ms Reset ratio Typicall...

Page 38: ...1 DSTPDIS 0 00 3000 00 0 01 PP operate delay Zn1 DSTPDIS 20 60000 ms 1 R0 zone 1 DSTPDIS 0 00 3000 00 0 01 X0 zone 1 DSTPDIS 0 00 3000 00 0 01 Factor K0 zone 1 DSTPDIS 0 0 4 0 0 1 Factor K0 angle Zn1...

Page 39: ...2 Forward 3 Reverse R1 zone 4 DSTPDIS 0 00 3000 00 0 01 X1 zone 4 DSTPDIS 0 00 3000 00 0 01 X1 reverse zone 4 DSTPDIS 0 00 3000 00 0 01 Z1 zone 4 DSTPDIS 0 01 3000 00 0 01 Z1 angle zone 4 DSTPDIS 15...

Page 40: ...n 2 3 4 5 Table 38 Local acceleration logic DSTPLAL main settings Parameter Function Value Range Step Load current value DSTPLAL 0 01 1 00 In 0 01 Minimum current DSTPLAL 0 01 1 00 In 0 01 Load releas...

Page 41: ...0 60000 ms 10 Wei Crd time CRWPSCH 0 60000 ms 10 Table 43 Communication logic for residual overcurrent RESCPSCH Characteristic Value Operate time accuracy 1 0 of the set value or 20 ms Table 44 Commun...

Page 42: ...et value High stage operate time 2 3 Minimum Typical Maximum 20 ms 23 ms 27 ms Reset time Typically 40 ms Reset ratio Typically 0 96 Retardation time 40 ms Operate time accuracy in definite time mode...

Page 43: ...LNPLDF 0 200 5 000 0 001 Table 49 Binary signal transfer BSTGAPC Characteristic Value Signalling delay Fiber optic link 5 ms Galvanic pilot wire link 10 ms Table 50 Switch onto fault protection CVPSOF...

Page 44: ...5 Peak to Peak No suppression P to P backup No suppression 1 Set Operate curve type IEC definite time Measurement mode default depends on stage current before fault 0 0 In fn 50 Hz fault current in o...

Page 45: ...n 2 3 4 5 1 Measurement mode and Pol quantity default current before fault 0 0 In voltage before fault 1 0 Un fn 50 Hz fault current in one phase with nominal frequency injected from random phase angl...

Page 46: ...to Peak No suppression 1 Measurement mode default depends on stage current before fault 0 0 In fn 50 Hz fault current in one phase with nominal frequency injected from random phase angle results based...

Page 47: ...8 ms 62 ms 66 ms Reset time Typically 40 ms Reset ratio Typically 0 96 Retardation time 30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse...

Page 48: ...de DEFxPDEF 1 Phase angle 2 IoSin 3 IoCos 4 Phase angle 80 5 Phase angle 88 1 For further reference see the Operating characteristics table Table 60 Three phase power directional element DPSRDIR main...

Page 49: ...ain settings Parameter Function Value Range Step Voltage start value EFPADM 0 01 2 00 Un 0 01 Directional mode EFPADM 1 Non directional 2 Forward 3 Reverse Operation mode EFPADM 1 Yo 2 Go 3 Bo 4 Yo Go...

Page 50: ...000 In 0 001 Operation mode MFADPSDE 1 Intermittent EF 2 Transient EF 3 General EF 4 Alarming EF Peak counter limit MFADPSDE 2 20 1 Table 66 Wattmetric based earth fault protection WPWDE Characteristi...

Page 51: ...the Operating characteristics table Table 68 Transient intermittent earth fault protection INTRPTEF Characteristic Value Operation accuracy Uo criteria with transient protection Depending on the freq...

Page 52: ...erate delay time HAEFPTOC 100 300000 ms 10 Operating curve type1 HAEFPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 Minimum operate time HAEFPTOC 100 200000 ms 1...

Page 53: ...ere n 2 3 4 5 Table 75 Phase discontinuity protection PDNSPTOC main settings Parameter Function Value Range Step Start value PDNSPTOC 10 100 1 Operate delay time PDNSPTOC 100 30000 ms 1 Min phase curr...

Page 54: ...Un fn 50 Hz undervoltage in one phase to phase with nominal frequency injected from random phase angle results based on statistical distribution of 1000 measurements 2 Includes the delay of the signa...

Page 55: ...1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms3 Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Start value 1 0 Un Volta...

Page 56: ...86 Positive sequence undervoltage protection PSPTUV Characteristic Value Operation accuracy Depending on the frequency of the measured voltage fn 2 Hz 1 5 of the set value or 0 002 Un Start time1 2 Mi...

Page 57: ...ltage before fault 0 0 Un fn 50 Hz negative sequence overvoltage with nominal frequency injected from random phase angle results based on statistical distribution of 1000 measurements 2 Includes the d...

Page 58: ...lue or 20 ms Operate time accuracy in inverse time mode 5 0 of the set value or 20 ms Suppression of harmonics 50 dB at f n fn where n 2 3 4 5 1 Measurement mode default current before fault 0 0 In fn...

Page 59: ...ings Parameter Function Value Range Step Start value OEPVPH 100 200 1 Operating curve type1 OEPVPH Definite or inverse time Curve type 5 15 17 18 19 20 Time multiplier OEPVPH 0 1 100 0 0 1 Operate del...

Page 60: ...ants T2PTTR Characteristic Value Operation accuracy Depending on the frequency of the measured current fn 2 Hz Current measurement 1 5 of the set value or 0 002 x In at currents in the range of 0 01 4...

Page 61: ...asurements Table 101 Three phase overload protection for shunt capacitor banks COLPTOC main settings Parameter Function Value Range Step Start value overload COLPTOC 0 30 1 50 In 0 01 Alarm start valu...

Page 62: ...ms Reset ratio Typically 0 96 Operate time accuracy in definite time mode 1 of the theoretical value or 20 ms Operate time accuracy in IDMT mode 5 of the theoretical value or 20 ms Suppression of har...

Page 63: ...TOC 1 11 1 Operate delay time SRCPTOC 120 360000 ms 1 Alarm delay time SRCPTOC 120 360000 ms 1 Table 108 Compensated neutral unbalance voltage protection CNUPTOV Characteristic Value Operation accurac...

Page 64: ...distribution of 1000 measurements 2 Measured with static signal output SSO Table 111 Directional negative sequence overcurrent protection DNSPDOC main settings Parameter Function Value Range Step Star...

Page 65: ...n 0 01 Voltage level 8 LVRTPTUV 0 00 1 20 xUn 0 01 Voltage level 9 LVRTPTUV 0 00 1 20 xUn 0 01 Voltage level 10 LVRTPTUV 0 00 1 20 xUn 0 01 Recovery time 1 LVRTPTUV 0 300000 ms 1 Recovery time 2 LVRTP...

Page 66: ...2 Typically 46 ms Reset time 50 ms Reset ratio Typically 0 96 Operate time accuracy 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Start value 0 05 Sn rea...

Page 67: ...er protection DOPPDPR main settings Parameter Function Value Range Step Start value DOPPDPR 0 01 2 00 Sn 0 01 Operate delay time DOPPDPR 40 300000 ms 10 Directional mode DOPPDPR 2 Forward 3 Reverse Po...

Page 68: ...des the delay of the signal output contact Table 123 Three phase underimpedance protection UZPDIS main settings Parameter Function Value Range Step Polar reach UZPDIS 1 6000 Zn 1 Operate delay time UZ...

Page 69: ...1 2 Typically 35 ms Reset time Typically 35 ms Reset ratio Typically 0 96 differential mode Typically 1 04 undervoltage mode Operate time accuracy 1 0 of the set value of 20 ms 1 fn 50 Hz results base...

Page 70: ...te delay time MREFPTOC 40 20000 ms 1 Alarm delay time MREFPTOC 40 200000 ms 1 Table 130 High impedance or flux balance based differential protection MHZPDIF Characteristic Value Operation accuracy Dep...

Page 71: ...0 300000 ms 10 Zone 1 reach OOSRPSB 1 100 1 Operate delay time OOSRPSB 20 60000 ms 10 Table 134 Negative sequence overcurrent protection for machines MNSPTOC Characteristic Value Operation accuracy De...

Page 72: ...40 ms Reset ratio Typically 1 04 Retardation time 35 ms Operate time accuracy in definite time mode mode 1 0 of the set value or 20 ms Table 137 Loss of phase undercurrent PHPTUC main settings Parame...

Page 73: ...r 20 ms Table 141 Motor load jam protection JAMPTOC main settings Parameter Function Value Range Step Operation JAMPTOC 1 on 5 off Start value JAMPTOC 0 10 10 00 In 0 01 Operate delay time JAMPTOC 100...

Page 74: ...acy Depending on the frequency of the measured current fn 2 Hz 1 5 of the set value or 0 002 In Start time1 2 Minimum Typical Maximum IFault 2 0 set Start value 23 ms 25 ms 28 ms Reset time Typically...

Page 75: ...Time constant normal MPTTR 80 4000 s 1 Time constant start MPTTR 80 4000 s 1 Env temperature mode MPTTR 1 FLC Only 2 Use input 3 Set Amb Temp Env temperature Set MPTTR 20 0 70 0 C 0 1 Operation MPTTR...

Page 76: ...e n 2 3 4 5 6 7 Reset time 40 ms Table 152 Underpower factor protection MPUPF main settings Parameter Function Value Range Step Min operate current MPUPF 0 05 0 65 In 0 01 Min operate voltage MPUPF 0...

Page 77: ...1 Not eliminated 2 Winding 1 3 Winding 2 4 Winding 1 and 2 5 Winding 3 6 Winding 1 and 3 7 Winding 2 and 3 8 Winding 1 2 3 Phase shift Wnd 1 2 TR3PTDF 0 0 359 9 0 1 Phase shift Wnd 1 3 TR3PTDF 0 0 35...

Page 78: ...PTDF 1 Not eliminated 2 Winding 1 3 Winding 2 4 Winding 1 and 2 Table 157 Numerical stabilized low impedance restricted earth fault protection LREFPNDF Characteristic Value Operation accuracy Dependin...

Page 79: ...002 In Start time1 2 Minimum Typical Maximum IFault 2 0 set Operate value IFault 10 0 set Operate value 16 ms 11 ms 21 ms 13 ms 23 ms 14 ms Reset time Typically 40 ms Reset ratio Typically 0 96 Retar...

Page 80: ...impedance differential protection HIxPDIF main settings Parameter Function Value Range Step Operate value HIxPDIF 1 0 200 0 In 1 0 Minimum operate time HIxPDIF 20 300000 ms 10 Table 163 Circuit break...

Page 81: ...ms3 13 ms2 6 ms3 Operation mode Light only 2 8 ms2 3 ms3 10 ms2 5 ms3 13 ms2 6 ms3 Reset time Typically 50 ms Reset ratio Typically 0 96 1 Phase start value 1 0 In current before fault 2 0 set Phase s...

Page 82: ...1000000 1 R1 line section A SCEFRFLO 0 000 1000 000 pu 0 001 X1 line section A SCEFRFLO 0 000 1000 000 pu 0 001 R0 line section A SCEFRFLO 0 000 1000 000 pu 0 001 X0 line section A SCEFRFLO 0 000 1000...

Page 83: ...SHDPFRQ 80 200000 ms 10 Operate Tm df dt LSHDPFRQ 120 200000 ms 10 Restore start Val LSHDPFRQ 0 800 1 200 fn 0 001 Restore delay time LSHDPFRQ 80 200000 ms 10 Table 174 Multipurpose protection MAPGAPC...

Page 84: ...inv 9 IEC Norm inv 10 IEC Very inv 11 IEC inv 12 IEC Ext inv 13 IEC S T inv 14 IEC L T inv 15 IEC Def Time 17 Programmable 18 RI type 19 RD type 20 UK rectifier Operating curve type voltage protectio...

Page 85: ...Autosynchronizer for generator breaker ASGCSYN Characteristic Value Measurement accuracy Depending on the frequency of the voltage measured fn 2 Hz Voltage difference 1 0 or 0 004 Un Frequency differ...

Page 86: ...20 1 00 Un 0 10 Voltage match mode ASGCSYN 1 Off 2 Variable Pulse 3 Variable Interval Frequency match mode ASGCSYN 1 Off 2 Variable Pulse 3 Variable Interval Table 182 Autosynchronizer for network br...

Page 87: ...CSYN 1 Off 2 Synchronous 3 Asynchronous 4 Command Dead bus voltage ASNSCSYN 0 1 0 8 Un 0 1 Live bus voltage ASNSCSYN 0 2 1 0 Un 0 1 Phase shift ASNSCSYN 180 180 1 Closing time of CB ASNSCSYN 40 250 ms...

Page 88: ...m Syn time SECRSYN 100 6000000 ms 10 Energizing time SECRSYN 100 60000 ms 10 Closing time of CB SECRSYN 40 250 ms 10 Table 186 Tap changer control with voltage regulator OL5ATCC Characteristic Value O...

Page 89: ...n mode OL5ATCC 1 Manual 2 Auto single 3 Parallel manual 4 Auto parallel 5 Input control 6 Command Parallel trafos OL5ATCC 0 10 1 Delay characteristic OL5ATCC 0 Inverse time 1 Definite time Band width...

Page 90: ...uning during EF Resistor healthy St PASANCR 0 Off 1 On Resistor repeats PASANCR 0 100 1 Resistor pause PASANCR 0 100000000 ms 1 Coil V Nom PASANCR 0 400000 V 1 Fix coil V Nom PASANCR 0 400000 V 1 Auxi...

Page 91: ...Range Step Cooling mode HSARSPTR 1 ONAN 2 ONAF 3 OFAF 4 ODAF Alarm level HSARSPTR 50 0 350 0 C 0 1 Warning level HSARSPTR 50 0 350 0 C 0 1 Alarm delay time HSARSPTR 0 3600000 ms 10 Warning delay time...

Page 92: ...scheme HZCCxSPVC main settings Parameter Function Value Range Step Start value HZCCxSPVC 1 0 100 0 In 0 1 Alarm delay time HZCCxSPVC 100 300000 ms 10 Alarm output mode HZCCxSPVC 1 Non latched 3 Lockou...

Page 93: ...ding on the frequency of the measured voltage 20 Hz f 70 Hz 1 5 of the set value or 0 002 Un 10 Hz f 20 Hz 4 0 of the set value or 0 002 Un Reset time Typically 40 ms Reset ratio Typically 1 04 Operat...

Page 94: ...RESCMMXU Characteristic Value Operation accuracy At the frequency f fn 0 5 or 0 002 In at currents in the range of 0 01 4 00 In Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 RMS No sup...

Page 95: ...power and energy measurement PEMMXU Characteristic Value Operation accuracy At all three currents in range 0 10 1 20 In At all three voltages in range 0 50 1 15 Un At the frequency fn 1 Hz 1 5 for ap...

Page 96: ...1 Nominal frequency 50 Hz Harmonics in the range 0 0 21 fundamental amplitude Table 217 Voltage total harmonic distortion DC component THD DC and individual harmonics VHMHAI main settings Parameter Fu...

Page 97: ...r 0 002 Un Reset ratio Typically 0 96 Table 221 Voltage unbalance VSQVUB main settings Parameter Function Value Range Step Operation VSQVUB 1 on 5 off Unb detection method VSQVUB 1 Neg Seq 2 Zero Seq...

Page 98: ...ty RDRE main settings Parameter function Value Range Step Record length RDRE 10 500 cycles 1 Pre trg length RDRE 0 100 1 Operation mode RDRE 1 Overwrite 2 Saturation Storage rate RDRE 32 16 8 samples...

Page 99: ...of the set value or 20 ms Table 224 Time delay off eight channels TOFPAGC Characteristic Value Operate time accuracy 1 0 of the set value or 20 ms Table 225 Time delay on eight channels TONGAPC Charac...

Page 100: ...ct information The complete order code can be created with detailed specification and the result can be printed and mailed Registration is required 25 Modification Sales Modification Sales is a concep...

Page 101: ...045621 LC SFP plug in connector for optical single mode media 100M 20 km 2RCA045622 LC SFP plug in connector for optical single mode media 100M 40 km 2RCA045623 Table 228 Mounting Item Order number Ba...

Page 102: ...nector 2RCA040474A0003 1 CT 1 VT ring lug type connector 2RCA041297A0004 5 CT ring lug type connector 2RCA041297A0001 5 VT ring lug type connector 2RCA041297A0002 1 CT 4 VT ring lug type connector 2RC...

Page 103: ...lay enables adding new protection functionalities whenever the protection and control needs are changing Table 231 Tools Description Version PCM600 2 9 HF1 or later Web browser IE 11 Microsoft Edge Go...

Page 104: ...4 N CT5 for residual X1 X2 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 5A 1 5A 1 5A 0 2 1A S1 S2 P2 P1 S1 P1 P2 S2 Positive Load flow Direction AIM1001 n a da dn A n L1 L2 L3 L1 L2 L3 current only GUI...

Page 105: ...CT5 X1 X2 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 5A 1 5A 1 5A 1 5A S1 S2 P2 P1 S1 P1 P2 S2 Positive Load flow Direction AIM1002 n a da dn A n L1 L2 L3 L1 L2 L3 1 5A N GUID E49A0352 50CA 4FE5 9D3D...

Page 106: ...1001 X1 4 5 7 8 DFF Sensor I Sensor U DFF X2 DFF DFF X3 DFF DFF 3 4 Sensor I Sensor U Sensor I Sensor U s1 s2 s1 s2 s1 s2 for residual current only 4 5 7 8 4 5 7 8 GUID 549B3B87 483B 4411 9790 D4FA852...

Page 107: ...1001 X1 4 5 7 8 DFF Sensor I Sensor U DFF X2 4 5 7 8 DFF DFF X3 4 5 7 8 DFF DFF 3 4 Sensor I Sensor U Sensor I Sensor U s1 s2 s1 s2 s1 s2 for residual current only GUID D37ABF6A CE39 4293 8D4B 1DA95A0...

Page 108: ...13 14 15 16 BI12 BI11 BI10 BI9 BI8 BI7 BI6 BI5 BI4 BI3 BI2 BI1 X2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 SO1 SO2 SO3 SO4 SO5 SO6 SO7 SO8 GUID 2F20AF34 230C 4E35 86AE A6F930250E3C V1 EN Figure 26 BI...

Page 109: ...BI6 BI5 BI4 BI3 BI2 BI1 X2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 SPO1 SPO3 SPO2 SPO4 SPO5 SPO6_TCS SPO7 SPO6 SPO8_TCS SPO8 I I GUID 46FF3F6E 0E8C 4FA7 8964 0480330AC56A V1 EN Figure 27 BIO1002 BIO1...

Page 110: ...10 11 12 14 13 15 16 17 18 Uaux X2 1 2 3 SO3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 PODP1 PO1_TCS PODP2 PODP3 PSM100x PO2_TCS PO3_TCS I I I GUID 6B2AB7B2 D285 4F90 A73D 40603FA7050B V1 EN Figure 28 PS...

Page 111: ...11 12 Ref RTD3 13 14 15 Ref RTD4 16 17 18 Ref RTD5 1 2 3 Ref RTD6 4 5 6 Ref RTD7 7 8 9 Ref RTD8 10 11 12 Ref RTD9 13 14 15 Ref RTD10 16 17 18 6 GUID 3EC6FABE BF3C 4789 AC2F 428C7D177126 V1 EN Figure...

Page 112: ...r input 1 Light sensor input 2 Light sensor input 3 Light sensor input 4 ARC1001 Slot A1 Slot A1 Slot A1 Slot A1 GUID 8CEA3233 FF96 49B8 B7BD 530C489CB9DD V1 EN Figure 30 Arc module 1MRS759144 A REX64...

Page 113: ...ound on the product page 30 References The www abb com substationautomation portal provides information on the entire range of distribution automation products and services The latest relevant informa...

Page 114: ...tage DPHLPDOC 3I 67P 51P 1 Three phase directional overcurrent protection high stage DPHHPDOC 3I 67P 51P 2 Non directional earth fault protection low stage EFLPTOC Io 51G 51N 1 Non directional earth f...

Page 115: ...nance protection current based SRCPTOC TD 55ITHD Compensated neutral unbalance voltage protection CNUPTOV CNU 59NU Directional negative sequence overcurrent protection DNSPDOC I2 67Q Low voltage ride...

Page 116: ...3I Io BF 50BF Three phase inrush detector INRPHAR 3I2f 68HB Master trip TRPPTRC Master Trip 94 86 Arc protection ARCSARC ARC AFD High impedance fault detection PHIZ HIF HIZ Fault locator SCEFRFLO FLO...

Page 117: ...ces MDSOPT OPTS OPTM Three phase remanent undervoltage supervision MSVPR 3U R 27R Measurement Three phase current measurement CMMXU 3I IA IB IC Sequence current measurement CSMSQI I1 I2 I0 I1 I2 I0 Re...

Page 118: ...MBSLPRT OR gate with two inputs OR OR OR OR gate with six inputs OR6 OR6 OR6 OR gate with twenty inputs OR20 OR20 OR20 AND gate with two inputs AND AND AND AND gate with six inputs AND6 AND6 AND6 AND...

Page 119: ...M Current switch CMSWI CMSWI CMSWI Phase current preprocessing ILTCTR ILTCTR ILTCTR Residual current preprocessing RESTCTR RESTCTR RESTCTR Phase and residual voltage preprocessing UTVTR UTVTR UTVTR SM...

Page 120: ...ion T_POS_CL T_POS_CL T_POS_CL Switching device status decoder OPEN position T_POS_OP T_POS_OP T_POS_OP Switching device status decoder OK status T_POS_OK T_POS_OK T_POS_OK Controllable gate 8 Channel...

Page 121: ...APP4 Shunt capacitor protection package APP5 Interconnection protection package APP6 Machine protection package APP7 Power transformer protection package APP8 Busbar protection package APP9 OLTC contr...

Page 122: ...HPTOC 3 PHIPTOC 3 DPHLPDOC 3 DPHHPDOC 3 EFLPTOC 3 EFHPTOC 3 EFIPTOC 3 DEFLPDEF 4 DEFHPDEF 4 DPSRDIR 2 DNZSRDIR 2 EFPADM 3 MFADPSDE 3 WPWDE 3 INTRPTEF 1 HAEFPTOC 1 NSPTOC 3 PDNSPTOC 1 ROVPTOV 4 PHPTUV...

Page 123: ...MPUPF 2 TR3PTDF 1 TR2PTDF 1 LREFPNDF 2 HREFPDIF 2 HIAPDIF 3 HIBPDIF 3 HICPDIF 3 CCBRBRF 3 INRPHAR 2 TRPPTRC 6 ARCSARC 4 PHIZ 1 SCEFRFLO 1 LSHDPFRQ 6 MAPGAPC 24 Control CBXCBR 3 P3SXSWI 6 DCXSWI 8 ESX...

Page 124: ...MXU 3 LDPRLRC 1 FMMXU 5 TPOSYLTC 1 Power quality CHMHAI 1 VHMHAI 1 PHQVVR 2 VSQVUB 2 Traditional LED indication LEDPTRC 1 LED 33 Logging functions RDRE 1 A1RADR 1 A2RADR 1 B1RBDR 1 B2RBDR 1 FLTRFRC 1...

Page 125: ...C 3 UDFCNT 12 CONTROL 1 EIHMI 1 ADDR 10 SUBR 10 MULR 10 DIVR 10 EQR 10 NER 10 GER 10 LER 10 VMSWI 3 CMSUM 1 CMSWI 3 ILTCTR 8 RESTCTR 8 UTVTR 8 SMVRCV 4 SMVSENDER 1 RCHLCCH 1 SCHLCCH 5 HMILCCH 1 GOOSER...

Page 126: ...APP 3 APP 4 APP 5 APP 6 APP 7 APP 8 APP 9 APP 10 APP 11 APP 12 APP 13 ADD 1 ADD 2 T_POS_OK 150 GATEGAPC 1 GSAL 1 HLTGAPC 1 SETI32GAPC 2 SETRGAPC 2 T_B16_TO_I32 10 T_I32_TO_B16 10 T_I32_TO_R 10 T_R_TO_...

Page 127: ...33 Document revision history Document revision date Product connectivity level PCL History A 2018 12 14 1 First release 1MRS759144 A REX640 Product version 1 ABB 127...

Page 128: ...128...

Page 129: ......

Page 130: ......

Page 131: ......

Page 132: ...BB Distribution Solutions Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 www abb com mediumvoltage www abb com relion Copyright 2018 ABB All rights reserved 1MRS759144 A...

Reviews: