Table 36. Distance protection (DSTPDIS) main settings, continued
Parameter
Function
Value (Range)
Step
Directional mode Zn3
DSTPDIS
1 = Non-directional
2 = Forward
3 = Reverse
-
R1 zone 3
DSTPDIS
0.00...3000.00 Ω
0.01
X1 zone 3
DSTPDIS
0.00...3000.00 Ω
0.01
X1 reverse zone 3
DSTPDIS
0.00...3000.00 Ω
0.01
Z1 zone 3
DSTPDIS
0.01...3000.00 Ω
0.01
Z1 angle zone 3
DSTPDIS
15.0...90.0°
0.1
Z1 reverse zone 3
DSTPDIS
0.00...3000.00 Ω
0.01
PP operate delay Zn3
DSTPDIS
20...60000 ms
1
R0 zone 3
DSTPDIS
0.00...3000.00 Ω
0.01
X0 zone 3
DSTPDIS
0.00...3000.00 Ω
0.01
Factor K0 zone 3
DSTPDIS
0.0...4.0
0.1
Factor K0 angle Zn3
DSTPDIS
-135...135°
1
Gnd operate Dl Zn3
DSTPDIS
20...60000 ms
1
Directional mode Zn4
DSTPDIS
1 = Non-directional
2 = Forward
3 = Reverse
-
R1 zone 4
DSTPDIS
0.00...3000.00 Ω
0.01
X1 zone 4
DSTPDIS
0.00...3000.00 Ω
0.01
X1 reverse zone 4
DSTPDIS
0.00...3000.00 Ω
0.01
Z1 zone 4
DSTPDIS
0.01...3000.00 Ω
0.01
Z1 angle zone 4
DSTPDIS
15.0...90.0°
0.1
Z1 reverse zone 4
DSTPDIS
0.00...3000.00 Ω
0.01
PP operate delay Zn4
DSTPDIS
20...60000 ms
1
R0 zone 4
DSTPDIS
0.00...3000.00 Ω
0.01
X0 zone 4
DSTPDIS
0.00...3000.00 Ω
0.01
Factor K0 zone 4
DSTPDIS
0.0...4.0
0.1
Factor K0 angle Zn4
DSTPDIS
-135...135°
1
Gnd operate Dl Zn4
DSTPDIS
20...60000 ms
1
Directional mode Zn5
DSTPDIS
1 = Non-directional
2 = Forward
3 = Reverse
-
R1 zone 5
DSTPDIS
0.00...3000.00 Ω
0.01
X1 zone 5
DSTPDIS
0.00...3000.00 Ω
0.01
X1 reverse zone 5
DSTPDIS
0.00...3000.00 Ω
0.01
Z1 zone 5
DSTPDIS
0.01...3000.00 Ω
0.01
Z1 angle zone 5
DSTPDIS
15.0...90.0°
0.1
Z1 reverse zone 5
DSTPDIS
0.00...3000.00 Ω
0.01
PP operate delay Zn5
DSTPDIS
20...60000 ms
1
1MRS759144 A