Table 189. Petersen coil controller (PASANCR) main settings
Parameter
Function
Value (Range)
Step
Compensation mode
PASANCR
1 = Absolute
2 = Relative
-
Detuning level
PASANCR
-100...100 A
1
Detuning level Rl
PASANCR
-100.0...100.0%
0.1
Tuning delay
PASANCR
0...3600 s
1
V Res variation
PASANCR
0.1...100.0 %U
n
0.1
Tuning mode
PASANCR
1 = Coil movement
2 = Resistor switching
-
V Res EF level
PASANCR
0.00...100.00 %U
n
0.01
EF mode
PASANCR
1 = Blocked during EF
2 = Resonance
3 = Tuning during EF
-
Resistor healthy St
PASANCR
0 = Off
1 = On
-
Resistor repeats
PASANCR
0...100
1
Resistor pause
PASANCR
0...100000000 ms
1
Coil V Nom
PASANCR
0...400000 V
1
Fix coil V Nom
PASANCR
0...400000 V
1
Auxiliary Wnd V Nom
PASANCR
0...10000 V
1
Controller mode
PASANCR
0 = Manual
1 = Automatic
-
Parallel resistor
PASANCR
0 = False
1 = True
-
R0Transformer
PASANCR
0...100 Ω
1
X0Transformer
PASANCR
0...100 Ω
1
Voltage measurement
PASANCR
1 = Busbar
2 = Coil
-
Resistor control
PASANCR
1 = OFF
2 = ON
3 = Automatic
-
Resistor Nom value
PASANCR
0.00...100.00 Ω
0.01
Fix coil value
PASANCR
0...10000 A
1
Fix coil type
PASANCR
1 = OFF
2 = ON
3 = Automatic
-
1MRS759144 A