The mode of all logical nodes located under the CTRL logical device is set with
Control mode
.
Control mode
is selected via the HMI or PCM600 path
Configuration/
Control/General
. By default,
Control mode
can only be set locally through LHMI.
Control mode
inherits its value from
Test mode
but
Control mode
”On”, “Blocked”
and “Off” can also be independently set.
Control mode
is also available via IEC 61850
communication (CTRL.LLN0.Mod).
Table 8:
Control mode
Control mode
Description
Control BEH_BLK
On
Normal operation
FALSE
Blocked
Control function commands blocked
TRUE
Off
Control functions disabled
FALSE
According to IEC 61850, the physical outputs to process should be blocked when the
device is set to blocked or test blocked mode. The usage depends on the ACT
configuration. In the protection blocking example the main trip from TRPPTRC1 is
blocked, and in the control blocking example CBXCBR1 is blocked. Both comply
with IEC 61850. In real applications some of PTRC’s might also be used for signalling
purposes (GOOSE) and blocking and interlocking via IO.
5.7.1
Protection blocking example
The physical outputs to process can be blocked with “IED blocked” and “IED test and
blocked” modes. If physical outputs need to be blocked, the application configuration
must block the signals or the function blocks that affect primary apparatuses. The
blocking scheme needs to use the
BEH_BLK
output of the PROTECTION function
block.
TRPPTRC1
BLOCK
OPERATE
RST_LKOUT
TRIP
CL_LKOUT
Protection
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
SG_LOGIC_SEL
SG_1_ACT
SG_2_ACT
SG_3_ACT
SG_4_ACT
SG_5_ACT
SG_6_ACT
BEH_TEST
BEH_BLK
TRPPTRC1_TRIP
GUID-BA7A67DB-3170-445A-9527-0809D251DA08 V1 EN
Figure 70:
Master trip TRPPTRC blocked using Protection function block
BEH_BLK
output
1MRS759117 A
Section 5
Protection and control engineering
REX640
93
Engineering Manual