GUID-1253B0CE-98D9-48BB-91B6-ADF29EC2CD7E V1 EN
Figure 94:
Creating a state
6.1.6
SLD Editor
SLD Editor is used to create single-line diagrams. In SLD Editor, bus bars, symbols
and text can be added from the object type window and links can be created between
symbols.
Once the symbols are placed on the HMI page, they must be linked in Application
Configuration to the corresponding function block that protects or controls the object
represented by the symbol. The values are updated by the protection relay either
periodically (measurement) or in case of an event.
Single-line diagrams support both ANSI and IEC standards. Single-line diagrams
created in ANSI can be changed to IEC and vice versa by changing the symbol
standard in PCM600. Custom symbols can be used in both ANSI and IEC standards.
In the object type window, symbols are grouped by their category.
The single-line diagram created in SLD Editor can be used on the main pages with a
special widget called SLDViewPort. The widget is available under the Container
group and its page property populates the list of SLD pages. The single-line diagram
size can be selected from the Object Properties pane. In ViewPort the single-line
diagram can be zoomed and paned on the LHMI.
Section 6
1MRS759117 A
LHMI engineering
114
REX640
Engineering Manual