5.  Process bus

The process bus utilizing IEC 61850-9-2 LE together with the
IEEE 1588 v2 accurate time synchronization provides sampled
measured values over the Ethernet communication. The
sampled measured values comprise four currents and four
voltages, that is, phase and residual currents as well as phase
and residual voltages. The residual voltage is calculated from
the measured phase voltages. The sample rate is 4000/4800
samples per second depending on the selected system
frequency.

6.  Self-supervision

The merging unit’s built-in self-supervision system continuously
monitors the state of the merging unit's hardware and the
operation of the merging unit's software. Any fault or
malfunction detected is used for alerting the operator.

A permanent merging unit fault blocks the application to
prevent incorrect operation.

7.  Secondary circuit supervision

Current circuit supervision is used for detecting faults in the
current transformer secondary circuits. Upon detecting a fault,
the current circuit supervision function activates an alarm. The
current circuit supervision function calculates the sum of the
phase currents from the protection cores and compares it to
the measured single reference current from a core balance
current transformer or from separate cores in the phase current
transformers.

The fuse failure supervision detects failures between the
voltage measurement circuit and the merging unit. The failures
are detected either by the negative sequence-based algorithm
or by the delta voltage and delta current algorithm. Upon
detecting a fault, the fuse failure supervision function activates
an alarm.

The trip-circuit supervision continuously monitors the
availability and operability of the trip circuit. It provides open
circuit monitoring both when the circuit breaker is in its closed
and in its open position. It also detects loss of circuit-breaker
control voltage.

8.  Access control

To protect the merging unit from unauthorized access and to
maintain information integrity, the merging unit is provided with

a four-level, role based authentication system with
administrator-programmable individual passwords for the
viewer, operator, engineer and administrator levels. The access
control applies to the Web HMI and PCM600.

9.  Inputs and outputs

Depending on the analog input option selected, the merging
unit is equipped either with three phase-current inputs, one
residual-current input and three phase-voltage inputs or
alternatively with one conventional residual current (Io 0.2/1 A)
input and three sensor inputs for the direct connection of three
combi sensors with RJ-45 connectors. As an alternative to the
combi sensors, separate current and voltage sensors can be
used utilizing adapters.

The phase current inputs are rated 1/5 A and the residual
current input is 0.2/1 A. The three phase voltage inputs cover
the rated voltages 60...210 V. Both phase-to-phase voltages
and phase-to-earth voltages can be connected. However,
phase-to-earth is recommended as the residual voltage can
only be derived from the phase-to-earth voltages.

Enhanced with optional hardware and software, the merging
unit also features three light detection channels for arc fault
detection in the circuit breaker, busbar and cable compartment
of metal enclosed indoor switchgear. The arc fault detection
sensor interface is available on the optional communication
module. The tripping decision is made by another protection
device also typically combining several different criteria like
checking of the fault current level.

Depending on the selected application configuration, the
merging unit includes either 4 PO + 2 SO (a total of 6 binary
outputs) or, when selected with the physical interface into the
switchgear primary equipment, 8 binary inputs and 4 PO + 2 SO
+ 3 HSO (a total of 9 binary outputs). The high-speed binary
outputs (HSO) decrease the total operate time typically with
4...6 ms compared to the normal power outputs.

All binary input and output contacts are freely configurable with
the signal matrix or application configuration functionality of
PCM600.

Substation Merging Unit

1MRS758420 B

SMU615

 

Product version: 1.0

 
 

ABB

9

Summary of Contents for Relion SMU615

Page 1: ...RELION Substation Merging Unit SMU615 Product Guide...

Page 2: ...Terminal diagrams 24 19 References 28 20 Functions codes and symbols 29 21 Document revision history 31 Disclaimer The information in this document is subject to change without notice and should not...

Page 3: ...8 v2 time synchronization and both conventional CT VT inputs and sensor inputs 2 Application configurations SMU615 is fully configured to perform its designed primary function in the system as a mergi...

Page 4: ...CDSARC 3 3 Control Circuit breaker control CBXCBR 1 Disconnector control DCXSWI 2 Earthing switch control ESXSWI 1 Disconnector position indication DCSXSWI 2 Earthing switch indication ESSXSWI 1 Other...

Page 5: ...tocols are able to overcome a failure of a link or switch with a zero switch over time In both the protocols each network node has two identical Ethernet ports dedicated for one network connection The...

Page 6: ...pled measured values to a protection relay As illustrated in Figure 1 SMU615 can measure the feeder currents with sensors and send them as sampled measured values over the Ethernet The protection rela...

Page 7: ...alues to protection relays In Figure 2 SMU615 measures the voltages in the substation and sends them as sampled measured values over the Ethernet Within the substation the protection relays with phase...

Page 8: ...ts in the substation and send them as sampled measured values over the Ethernet The centralized protection device in the substation can receive the SMVs from each SMU615 over the Ethernet and use thes...

Page 9: ...and to maintain information integrity the merging unit is provided with a four level role based authentication system with administrator programmable individual passwords for the viewer operator engi...

Page 10: ...reaker and to indicate the position of one circuit breaker disconnector and earthing switch The application configuration can be further modified to release some binary outputs which have been origina...

Page 11: ...tart up threshold 19 2 V DC 24 V DC 80 Burden of auxiliary voltage supply under quiescent Pq operating condition DC 13 0 W nominal 18 0 W max AC 16 0 W nominal 21 0 W max DC 13 0 W nominal 18 0 W max...

Page 12: ...250 V DC Current drain 1 6 1 9 mA Power consumption 31 0 570 0 mW Threshold voltage 16 176 V DC Reaction time 3 ms Table 9 Signal output X100 SO1 Description Value Rated voltage 250 V AC DC Continuou...

Page 13: ...e 250 V AC DC Continuous contact carry 8 A Make and carry for 3 0 s 15 A Make and carry for 0 5 s 30 A Breaking capacity when the control circuit time constant L R 40 ms at 48 110 220 V DC 5 A 3 A 1 A...

Page 14: ...80 120 of Un Amplitude 0 5 Angle 1 Residual voltage calculated 1 100 of Un Amplitude 0 5 or 0 001 Un Angle 2 1 In the 80 A 0 150 V at 50 Hz sensor applications the maximum range depends on the applica...

Page 15: ...unity test IEC 60255 26 2013 IEC 61000 4 5 2005 GB 14598 26 2015 Communication 0 5 kV line to earth 1 kV line to earth 2 kV line to earth Other ports 0 5 kV line to earth 1 kV line to earth 2 kV line...

Page 16: ...1 min communication IEC 60255 272013 Impulse voltage test 5 kV 1 2 50 s 0 5 J 1 kV 1 2 50 s 0 5 J communication IEC 60255 272013 Insulation resistance measurements 100 M 500 V DC IEC 60255 272013 Tabl...

Page 17: ...EN 60255 27 2013 EN 60255 1 2009 Table 24 EMC compliance Description Reference EMC directive 2004 108 EC Standard EN 60255 26 2013 Table 25 RoHS compliance Description Complies with RoHS directive 200...

Page 18: ...x operate current CCSPVC 1 00 5 00 In 0 01 Table 29 Fuse failure supervision SEQSPVC Characteristic Value Operate time1 NPS function UFault 1 1 set Neg Seq voltage Lev 33 ms UFault 5 0 set Neg Seq vol...

Page 19: ...ic Value Operation accuracy Depending on the frequency of the current measured f fn 2 Hz 0 5 or 0 002 In at currents in the range of 0 01 4 00 In Suppression of harmonics DFT 50 dB at f n fn where n 2...

Page 20: ...power S 1 5 for active power P and active energy1 1 5 for reactive power Q and reactive energy2 0 015 for power factor Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 PF 0 5 which equa...

Page 21: ...uts for one or two merging units Alternatively the merging units can be mounted in 19 instrument cabinets by means of 4U Combiflex equipment frames For routine testing purposes the merging unit cases...

Page 22: ...kit 1MRS050697 Inclined semi flush mounting kit 1MRS050831 19 rack mounting kit with cut out for one merging unit 1MRS050694 19 rack mounting kit with cut out for two merging units 1MRS050695 Mountin...

Page 23: ...EC 61850 communication configuration GOOSE communication configuration Phasor diagram viewing Event viewing Saving of event data on the user s PC Online monitoring Supported 17 Cyber security The merg...

Page 24: ...Optional 2 The IED features an automatic short circuit mechanism in the CT connector when plug in unit is detached 2 X120 1 2 3 4 5 6 7 8 9 10 11 12 14 Io IL1 IL2 IL3 1 5A N 1 5A N 1 5A N 0 2 1A N 13...

Page 25: ...SO2 TCS2 PO4 SO1 TCS1 PO3 PO2 PO1 IRF Uaux 20 1 Order selectable Optional X130 1 2 X131 4 5 IL1 7 8 U1 X132 4 5 IL2 7 8 U2 X133 4 5 IL3 7 8 U3 Io 0 2 1A N GUID 3918EC87 B65A 4527 B026 105423ACA033 V1...

Page 26: ...13 U1 U2 U3 60 N 210V 60 N 210V 60 N 210V 1 Order selectable Optional 2 The IED features an automatic short circuit mechanism in the CT connector when plug in unit is detached 2 3 5 6 7 BI 6 BI 5 BI...

Page 27: ...1 2 X131 4 5 IL1 7 8 U1 X132 4 5 IL2 7 8 U2 X133 4 5 IL3 7 8 U3 Io 0 2 1A N 1 Order selectable Optional 2 3 5 6 7 BI 6 BI 5 BI 4 BI 3 BI 2 BI 8 BI 7 10 8 BI 1 1 4 9 X110 15 16 19 23 20 24 HSO3 HSO2 HS...

Page 28: ...nces The www abb com substationautomation portal provides information on the entire range of distribution automation products and services Substation Merging Unit 1MRS758420 B SMU615 Product version 1...

Page 29: ...on TCSSCBR1 TCS 1 TCM 1 TCSSCBR2 TCS 2 TCM 2 Current circuit supervision CCSPVC1 MCS 3I 1 MCS 3I 1 Fuse failure supervision SEQSPVC1 FUSEF 1 60 1 Arc detection ARCDSARC1 ARCD 1 AFD 1 ARCDSARC2 ARCD 2...

Page 30: ...N 3 TON 3 TONGAPC4 TON 4 TON 4 Set reset 8 pcs SRGAPC1 SR 1 SR 1 SRGAPC2 SR 2 SR 2 SRGAPC3 SR 3 SR 3 SRGAPC4 SR 4 SR 4 Move 8 pcs MVGAPC1 MV 1 MV 1 MVGAPC2 MV 2 MV 2 Generic control point 16 pcs SPCGA...

Page 31: ...cument revision history Document revision date Product version History A 2017 09 26 1 0 First release B 2019 05 17 1 0 Content updated Substation Merging Unit 1MRS758420 B SMU615 Product version 1 0 A...

Page 32: ...ribution Solutions Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 www abb com mediumvoltage www abb com substationautomation Copyright 2019 ABB All rights reserved 1MRS7...

Reviews: