109
Table 5.1.16.-2
Warning codes
Fault
Weight value
Battery low
1
Trip-circuit supervision
a)
2
Power supply module temperature high
4
Communication module faulty or missing
8
RTD module faulty
16
Temperature sensor range error
32
Sensor circuit open or shorted (RTD1)
64
Sensor circuit open or shorted (RTD2)
128
Sensor circuit open or shorted (RTD3)
256
Sensor circuit open or shorted (RTD4)
512
Sensor circuit open or shorted (RTD5)
1024
Sensor circuit open or shorted (RTD6)
2048
Thermistor circuit open or shorted (Thermistor1)
4096
Thermistor circuit open or shorted (Thermistor2)
8192
∑
16383
a)
The external fault warning can be routed to SO2 with SGF1/8.
For further information on warnings, refer to the Operator
’
s Manual.
5.1.16.1.
Self-supervision of the RTD module
Each input sample is validated before it is fed into the filter algorithm. The samples
are validated by measuring an internally set reference voltage immediately after the
inputs have been sampled. If the measured offset voltage deviates from the set value
by more than 1.5 per cent from the measuring range, the sample will be discarded. If
the fault has not disappeared on expiration of the filter time of eight seconds, all
inputs will automatically be set out of operation to indicate a hardware fault. Should
the fault later disappear, the inputs will be re-enabled. This will prevent most sudden
hardware faults from affecting the measured value.
To ensure that the specified measurement accuracy is achieved, a more thorough test
of the hardware will be performed as part of the continuous self-calibration
procedure to identify errors which degrade the measurement accuracy. If the self-
calibration of the RTD module fails, all inputs will automatically be set out of
operation to indicate a hardware fault. Should the self-calibration later succeed, the
inputs will be re-enabled.
Additionally, a single input will be set out of operation if the measured value is
outside the specified limits (-4%...104%) or if an open-loop or a short-circuit
condition is detected.
5.1.17.
Relay parameterization
The parameters of the relay can be set either locally via the HMI or externally via
serial communication with Relay Setting Tool.
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537