131
In this case, a safe stall time setting of 23 seconds is selected from the trip
curves at prior load 1 x FLA, permitting a start-up time slightly longer than
the one stated by the motor manufacturer; see the figure below.
t/s
I/I
n
50
10
20
5
1
2
3
4
30
40
1
2
3
4
5
10
6
8
1.05
t
6x
120
60
30
20
15
10
5
2.5
[
s
]
A051488
Fig. 6.1.2.2.-2
Selected safe stall time 23 s
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537
Summary of Contents for REM 610
Page 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 124: ...124 ...
Page 144: ...144 ...
Page 154: ...154 ...
Page 157: ......