153
Description
Parameter
(channel 0)
Setting range
Default
setting
Customer
’
s
setting
Rear communication
protocol
V203
0 = SPA
1 = IEC_103
2 = Modbus RTU
3 = Modbus ASCII
0
Connection type
V204
0 = loop
1 = star
0
Line-idle state
V205
0 = light off
1 = light on
0
Optional communication
module
V206
0 = not in use
1 = in use
0
Table 8.-4
Parameters for the disturbance recorder
Description
Parameter
(channel 0)
Setting range
Default
setting
Customer
’
s
setting
Sampling rate
M15
800/960 Hz
400/480 Hz
50/60 Hz
800 Hz
Station identification/unit
number
M18
0...9999
0
Name of the motor drive
M20
Max 16 characters - ABB -
Analog channel conversion
factor and unit for I
a
, I
b
and
I
c
M80, M81,
M82
Factor 0...65535,
unit (A, kA), e.g. 10,
kA
00001,CT
Analog channel conversion
factor and unit for the
ground-fault current
M83
Factor 0...65535,
unit (A, kA), e.g. 10,
kA
00001,CT
Internal trigger signals'
checksum
V236
0...8191
2728
Internal trigger signal's edge V237
0...8191
0
Checksum of internal signal
storing mask
V238
0...8191
6842
Post-triggering recording
length
V240
0...100%
50 %
External trigger signal's
checksum
V241
0...31
0
External trigger signal's
edge
V242
0...31
0
Checksum of external signal
storing mask
V243
0...31
0
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537
Summary of Contents for REM 610
Page 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 124: ...124 ...
Page 144: ...144 ...
Page 154: ...154 ...
Page 157: ......