Table 5.1.4.12.-1
Setting values
Setting
Description
Setting range
Default setting
FLA SEC.
FLA secondary scaling factor 0.50...2.50
a)
1
t
6x
Safe stall time
2...120 s
b)
2 s
p
Weighting factor
20...100%
50 %
K
c
Time constant dial
1...64
1
49 ALARM
Prior alarm level
50...100%
95%
49 RESTDIS
Restart disable level
20...80%
40%
T
amb
Ambient temperature
0...70°C
40°C
48/14 PICKUP/FLA
Start-up current for motor or
pickup value of element 48/14
1.00
…
10.0 x FLA
1.00 x FLA
48/14 TDLY
Start-up time for motor or
operate time of element 48/14
0.30...80.0 s
0.30 s
50P/FLA
Pickup value of element 50P
0.50...20.0 x FLA
1.00 x FLA
50P TDLY
Operate time of element 50P
0.05...30.0 s
0.05 s
51N/ I
n
CT
Pickup value of element 51N
1.0...100% I
n
CT
1.0% I
n
CT
51N TDLY
Operate time of element 51N 0.05...300 s
0.05 s
37/ FLA
Pickup value of element 37
30...80% FLA
50% FLA
37 TDLY
Operate time of element 37
2...600 s
2 s
46 PICKUP/ FLA
Pickup value of element 46
0.10
…
0.50 x FLA
0.20 x FLA
46 TDIAL
Time constant of element 46 at
IDMT characteristic
5...100
5
66
Restart disable value
5...500 s
5 s
66 COOL/
Δ
t
Countdown rate of start-up
time counter
2...250 s/h
2 s/h
Trip Fail
Operate time of CBFAIL
0.10...60.0 s
0.10 s
RTD1A
Alarm value RTD1A
0...200°C
0°C
RTD1A TDLY
Operate time RTD1A TDLY
1...100 s
1 s
RTD1T
Trip value RTD1T
0...200°C
0°C
RTD1T TDLY
Operate time RTD1T TDLY
1...100 s
1 s
48
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537
Summary of Contents for REM 610
Page 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 124: ...124 ...
Page 144: ...144 ...
Page 154: ...154 ...
Page 157: ......