51
Switch
Function
Default setting
SGF1/5
Minimum pulse length for PO1, PO2 and PO3
0
*
0=80 ms
*
1=40 ms
The latching feature being selected for PO1, PO2
and PO3 will override this function.
SGF1/6
CBFAIL
0
*
0 =CBFAIL is not in use
*
1 = the signal to PO1 will start a timer which will generate a
delayed signal to PO2, provided that the fault is not cleared
before the CBFAIL operate time has elapsed.
SGF1/7
Restart disable function
0
*
When the switch is in position 0, the restart disable signal will
be routed to PO3.
*
When the switch is in position 1, the restart disable signal will
not be routed to PO3.
SGF1/8
External fault warning
0
*
When the switch is in position 1, the warning signal from the
trip-circuit supervision is routed to SO2.
To avoid conflicts, SGR5 should be set to 0 when
SGF1/8=1.
Σ
SGF1
0
Table 5.1.4.12.-3
SGF2
Switch
Function
Default setting
SGF2/1
Operation mode of the alarm target of element 49
0
SGF2/2
Operation mode of the pickup target of element 48/14
a)
0
SGF2/3
Operation mode of the pickup target of element 50P
a)
0
SGF2/4
Operation mode of the pickup target of element 37
a)
0
SGF2/5
Operation mode of the pickup target of element 51N
0
SGF2/6
Operation mode of the pickup target of element 46
0
SGF2/7
Operation mode of the alarm target of element 49/38-1
0
SGF2/8
Operation mode of the alarm target of element 49/38-2
0
*
0 = the pickup target will automatically be cleared once the fault
has disappeared
*
1 = latching. The pickup target will remain active although the
fault has disappeared.
Σ
SGF2
0
a)
In addition, the phase(s) which caused the pickup will be shown on the LCD.
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537