53
Switch
Function
Default setting
SGF5/8
Selection of the latching feature for programmable LED8
0
*
When the switch is in position 0 and the signal routed to the
LED is reset, the programmable LED will be cleared.
*
When the switch is in position 1, the programmable LED will
remain lit although the signal routed to the LED is reset.
A latched programmable LED can be cleared either via the HMI,
a digital input or the serial bus.
Σ
SGF5
0
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of switchgroup
SGB1, the DI2 signal with those of SGB2, and so forth.
Table 5.1.4.12.-7
SGB1...SGB5
Switch
Function
Default setting
SGB1...5/1
*
0 = targets are not cleared by the digital input signal
*
1 = targets are cleared by the digital input signal
0
SGB1...5/2
*
0 = targets are not cleared and latched output contacts are not
unlatched by the digital input signal
*
1 = targets are cleared and latched output contacts are
unlatched by the digital input signal
0
SGB1...5/3
*
0 = targets and memorized values are not cleared and latched
output contacts are not unlatched by the digital input signal
*
1 = targets and memorized values are cleared and latched
output contacts are unlatched by the digital input signal
0
SGB1...5/4
Switching between setting groups 1 and 2 using the digital input
*
0 = the setting group cannot be changed using the digital input
*
1 = the setting group is changed by using the digital input.
When the digital input is energized, setting group 2 will be
activated, if not, setting group 1 will be activated.
When SGB1...5/4 is set to 1, it is important that the
switch has the same setting in both setting
groups.
0
SGB1...5/5
External tripping by the digital input signal
0
SGB1...5/6
External triggering of the CBFAIL by the digital input signal
0
SGB1...5/7
External restart disable by the digital input signal
0
SGB1...5/8
Activating the emergency start by the digital input signal
0
SGB1...5/9
Blocking of element (48/14 PICKUP)
2
x (48/14 TDLY) or 48/14 by
the digital input signal (speed switch input)
0
SGB1...5/10
Blocking of element 50P by the digital input signal
0
SGB1...5/11
Blocking of element 37 by the digital input signal
0
SGB1...5/12
Blocking of element 51N by the digital input signal
0
SGB1...5/13
Blocking of element 46 by the digital input signal
0
SGB1...5/14
Time synchronization by the digital input signal
0
Σ
SGB1...5
0
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537
Summary of Contents for REM 610
Page 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 124: ...124 ...
Page 144: ...144 ...
Page 154: ...154 ...
Page 157: ......