Feature
Value
Resetting time, typical/maximum
40/50 ms
Retardation time
30 ms
Drop-off/pick-up ratio, typical
0.96
Operate time accuracy at definite-time
characteristic
±2% of the set operate time or ±25 ms
Operation accuracy
±3% of the set pickup value
Table 5.1.4.13.-5
Element 37
Feature
Value
Set pickup value, 51P
*
at definite-time characteristic
30...80% FLA
pickup time, typical
300 ms
Time/current characteristic
*
definite time operate time, 27P-1 TDLY
2...600 s
Resetting time, typical/maximum
300/350 ms
Drop-off/pick-up ratio, typical
1.1
Disable of 37
<12% FLA
Operate time accuracy at
*
definite-time characteristic
±3% of the set operate time or 100 ms
Operation accuracy
±3% of the set pickup value or +0.5% FLA
Table 5.1.4.13.-6
Element 51N
Feature
Value
Set pickup value, 51N
*
at definite-time characteristic
1.0...100% I
n
CT
Pickup time, typical
50 ms
Time/current characteristic
*
definite time operate time, 51N TDLY
0.05...300 s
Resetting time, typical/maximum
40/50 ms
Retardation time
30 ms
Drop-off/pick-up ratio, typical
0.96
Operate time accuracy at definite-time
characteristic
±2% of the set operate time or ±25 ms
Operation accuracy
*
1.0...10.0% I
n
CT
±5% of the set pickup value
*
10.0...100% I
n
CT
±3% of the set pickup value
Table 5.1.4.13.-7
Element 46
Feature
Value
Set pickup value, 46
*
at IDMT characteristic
0.10...0.50 x FLA
Pickup time, typical
100 ms
Time/current characteristic
*
IDMT time constant, 46 TDIAL
5...100
Resetting time, typical/maximum
130/200 ms
60
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537