87
Table 5.1.14.1.-14
Fault record
Address
Signal name
Range
Comment
601
Latest selection code
a)
1...2
1 = read oldest unread record
2 = read oldest stored record
602
Sequence number
1...999
603
Unread records left
0...6
604
Time stamp of the recorded data, date
2 bytes: YY.MM
605
Time stamp of the recorded data, time
2 bytes: DD.HH
606
Time stamp of the recorded data, date and time
2 bytes: MM.SS
607
Time stamp of the recorded data, time
0...999
0...999 ms
608
Phase current I
a
0...5000
0...50 x FLA
609
Phase current I
b
0...5000
0...50 x FLA
610
Phase current I
c
0...5000
0...50 x FLA
611
Ground-fault current
0...8000
0...800.0%
612
NPS current
0...5000
0...50 x FLA
613
Thermal stress value
0...100
0...100%
614
Number of motor start ups
0...999
0...999
615
Thermal level at start
0...106
0...106%
616
Thermal level at end
0...106
0...106%
617
Temperature from RTD1
-40...999
-40...999°C
b)
618
Temperature from RTD2
-40...999
-40...999°C
b)
619
Temperature from RTD3
-40...999
-40...999°C
b)
620
Temperature from RTD4
-40...999
-40...999°C
b)
621
Temperature from RTD5
-40...999
-40...999°C
b)
622
Temperature from RTD6
-40...999
-40...999°C
b)
623
Thermistor 1, resistance value
0...200
0...20 k
Ω
c)
624
Thermistor 2, resistance value
0...200
0...20 k
Ω
c)
625
Pickup duration of element 49/38-1, alarm
0...100
0...100%
626
Pickup duration of element 49/38-1, trip
0...100
0...100%
627
Pickup duration of element 49/38-2, alarm
0...100
0...100%
628
Pickup duration of element 49/38-2, trip
0...100
0...100%
629
Pickup duration, element (48/14 PICKUP)
2
x (48/14
TDLY) or 48/14
0...100
0...100%
630
Pickup duration, element 50P-1
0...100
0...100%
631
Pickup duration, element 46
0...100
0...100%
632
Pickup duration, element 51N
0...100
0...100%
633
Pickup duration, element 37
0...100
0...100%
a)
Readable and writeable register.
b)
If the input is out of operation or the optional RTD module has not been installed, the value -32768 will be returned.
c)
If the input is out of operation or the optional RTD module has not been installed, the value 655 will be returned.
Structure 3
This structure contains Modbus event records. Refer to Event records earlier in this
section for the reading method.
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537