Table 5.1.14.1.-15
Event record
Address
Signal name
Range
Comment
671
Latest selection code
a)
1...3
1 = read oldest unread record
2 = read oldest stored record
3 = clear Modbus event buffer
-1...-99
-1...-99 = move to the nth
newest record
672
Sequence number
1...999
673
Unread records left
0...99
674
Time stamp of the event, date
2 bytes: YY.MM
675
Time stamp of the event, date and time
2 bytes: DD.HH
676
Time stamp of the event, time
2 bytes: MM.SS
677
Time stamp of the event, time
0...999
0...999 ms
678
Event data
See Table 5.1.14.1.-16 for
Modbus DI-point events and
Table 5.1.14.1.-17 for
informative events
679
a)
Readable and writeable register.
Table 5.1.14.1.-16
Modbus DI-point event
Address Name
Range
Comment
678
0
Modbus DI-point
1...99
MSB = 0
679
Modbus DI value
0...1
Table 5.1.14.1.-17
Informative event
Address Name
Range
Comment
678
1
SPA channel
0...3
MSB = 1
679
SPA event
0...63
Structure 4
The relay's real-time clock is stored in this structure. It can be updated by presetting
the whole register structure in one Modbus transaction.
Table 5.1.14.1.-18
Real-time clock structure
Address
Description
Range
721
Year
0...99
722
Month
1...12
723
Day
1...31
724
Hour
0...23
725
Minute
0...59
726
Second
0...59
727
Hundredth of a second
0...99
88
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537
Summary of Contents for REM 610
Page 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 124: ...124 ...
Page 144: ...144 ...
Page 154: ...154 ...
Page 157: ......