Variable
Actual
settings (R),
channel 0
Group/
Channel 1 (R,
W, P)
Group/
Channel 2 (R,
W, P)
Setting range
Pickup value of element
46
S15
b)
1S15
2S15
0.10
…
0.50 x
FLA
Time constant of element
46
S16
1S16
2S16
5...100
Restart disable value
S17
1S17
2S17
5...500 s
Countdown rate of start-
up time counter
S18
1S18
2S18
2...250 s/h
Operate time of CBFAIL
S19
1S19
2S19
0.10...60.0 s
Alarm value RTD1A
S20
b)
1S20
2S20
0...200°C
Operate time RTD1A
TDLY
S26
1S26
2S26
1...100 s
Trip value RTD1T
S32
b)
1S32
2S32
0...200°C
Operate time RTD1T
TDLY
S38
1S38
2S38
1...100 s
Alarm value RTD2A
S21
b)
1S21
2S21
0...200°C
Operate time RTD2A
TDLY
S27
1S27
2S27
1...100 s
Trip value RTD2T
S33
b)
1S33
2S33
0...200°C
Operate time RTD2T
TDLY
S39
1S39
2S39
1...100 s
Alarm value RTD3A
S22
b)
1S22
2S22
0...200°C
Operate time RTD3A
TDLY
S28
1S28
2S28
1...100 s
Trip value RTD3T
S34
b)
1S34
2S34
0...200°C
Operate time RTD3T
TDLY
S40
1S40
2S40
1...100 s
Alarm value RTD4A
S23
b)
1S23
2S23
0...200°C
Operate time RTD4A
TDLY
S29
1S29
2S29
1...100 s
Trip value RTD4T
S35
b)
1S35
2S35
0...200°C
Operate time RTD4T
TDLY
S41
1S41
2S41
1...100 s
Alarm value RTD5A
S24
b)
1S24
2S24
0...200°C
Operate time RTD5A
TDLY
S30
1S30
2S30
1...100 s
Trip value RTD5T
S36
b)
1S36
2S36
0...200°C
Operate time RTD5T
TDLY
S42
1S42
2S21
1...100 s
Alarm value RTD6A
S25
b)
1S25
2S25
0...200°C
Operate time RTD6A
TDLY
S31
1S31
2S31
1...100 s
Trip value RTD6T
S37
b)
1S37
2S37
0...200°C
Operate time RTD6T
TDLY
S43
1S43
2S43
1...100 s
Trip value PTC1
S44
b)
1S44
2S44
0.1...15.0 k
Ω
Trip value PTC2
S45
b)
1S45
2S45
0.1...15.0 k
Ω
90
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537