93
Recorded data
Parameter
(R)
Value
Number of pickups of element (48/
14 PICKUP)2 x (48/14 TDLY) or
48/14
V4
0...999
Number of pickups of element 50P
V5
0...999
Number of pickups of element 51N
V6
0...999
Number of pickups of element 37
V7
0...999
Number of pickups of element 46
V8
0...999
The last five recorded values can be read with parameters
V1
...
V28
on channels
1...5. Event n denotes the last recorded value, n-1 the next one, and so forth.
Table 5.1.15.-3
Recorded data: Channels 1...5
Recorded data
Event (R)
Value
n
Channel 1
n-1
Channel 2
n-2
Channel 3
n-3
Channel 4
n-4
Channel 5
Phase current I
a
1V1
2V1
3V1
4V1
5V1
0...50 x FLA
Phase current I
b
1V2
2V2
3V2
4V2
5V2
0...50 x FLA
Phase current I
b
1V3
2V3
3V3
4V3
5V3
0...50 x FLA
Ground-fault
current
1V4
2V4
3V4
4V4
5V4
0...800% I
n
CT
NPS current
1V5
2V5
3V5
4V5
5V5
0...50 x FLA
Thermal stress
value
1V6
2V6
3V6
4V6
5V6
0...100%
Number of
motor start ups
1V7
2V7
3V7
4V7
5V7
0...999
Thermal level at
start
1V8
2V8
3V8
4V8
5V8
0...106%
Thermal level at
end
1V9
2V9
3V9
4V9
5V9
0...106%
Temperature
from RTD1
1V10
2V10
3V10
4V10
5V10
-40...+999°C
Temperature
from RTD2
1V11
2V11
3V11
4V11
5V11
-40...+999°C
Temperature
from RTD3
1V12
2V12
3V12
4V12
5V12
-40...+999°C
Temperature
from RTD4
1V13
2V13
3V13
4V13
5V13
-40...+999°C
Temperature
from RTD5
1V14
2V14
3V14
4V14
5V14
-40...+999°C
Temperature
from RTD6
1V15
2V15
3V15
4V15
5V15
-40...+999°C
Thermistor1,
resistance value
1V16
2V16
3V16
4V16
5V16
0...20 k
Ω
Thermistor2,
resistance value
1V17
2V17
3V17
4V17
5V17
0...20 k
Ω
Pickup duration
of element 49/
38-1, alarm
1V18
2V18
3V18
4V18
5V18
0...100%
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537
Summary of Contents for REM 610
Page 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 124: ...124 ...
Page 144: ...144 ...
Page 154: ...154 ...
Page 157: ......