119
5.2.3.
Technical data
Table 5.2.3.-1
Dimensions (for dimension drawings, refer to the Installa-
tion Manual)
Width, frame 177 mm, case 164 mm
Height, frame 177 mm (4U), case 160 mm
Depth, case 149.3 mm
Weight of the relay
~
3.5 kg
Weight of the spare unit
~
1.8 kg
Table 5.2.3.-2
Power supply
U
aux
rated:
-REM610CxxHxxx
U
r
= 100/110/120/220/240 V AC
U
r
= 110/125/220/250 V DC
-REM610CxxLxxx
U
r
= 24/48/60 V DC
U
aux
variation (temporary):
-REM610CxxHxxx
85...110% of U
r
(AC)
80...120% of U
r
(DC)
-REM610CxxLxxx
80...120% of U
r
(DC)
Burden of auxiliary voltage supply under quiescent
(P
q
)/operating condition
<9 W/13 W
Ripple in the DC auxiliary voltage
Max 12% of the DC value (at
frequency of 100 Hz)
Interruption time in the auxiliary DC voltage without
resetting the relay
<50 ms at U
aux
rated
Time to trip from switching on the auxiliary voltage
a)
<350 ms
Internal over temperature limit
+100°C
Fuse type
T2A/250 V
a)
Time to trip of element 50P and 51N.
Table 5.2.3.-3
Energizing inputs
Rated frequency
50/60 Hz
±
5
Hz
Rated current, I
n
(CT)
1 A
5 A
Thermal withstand capability:
*
continuously
4 A
20 A
*
for 1 s
100 A
500 A
*
for 10 s
25 A
100 A
Dynamic current withstand:
*
half-wave value
250 A
1250 A
Input impedance
<100 m
Ω
<20 m
Ω
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537