Event
Weighting factor Default value of
triggering mask,
V236
Default value of
triggering edge,
V237
Default value of
storing mask,
V238
Trip of element
37
128
1
0
1
Pickup of
element 51N
256
0
0
0
Trip of element
51N
512
1
0
1
Pickup of
element 46
1024
0
0
0
Trip of element
46
2048
1
0
1
Motor start up
4096
0
0
1
Σ
2728
0
6842
a)
0 = rising edge, 1 = falling edge.
Table 5.1.15.-6
Disturbance recorder external triggering and storing
Event
Weighting factor Default value of
triggering mask,
V241
Default value of
triggering edge,
V242
a)
Default value of
storing mask,
V243
DI1
1
0
0
0
DI2
2
0
0
0
DI3
4
0
0
0
DI4
8
0
0
0
DI5
16
0
0
0
Σ
0
0
0
a)
0 = rising edge; 1 = falling edge.
Table 5.1.15.-7
Control parameters
Description
Parameter
R, W, P
Value
Reading of the event buffer
L
R
Time, channel number and event code
Re-reading of the event buffer
B
R
Time, channel number and event code
Reading of relay state data
C
R
0 = Normal state
1 = The relay has been subject to an
automatic reset
2 = Overflow of the event buffer
3 = Both 1 and 2
Resetting of relay state data
C
W
0 = Reset E50 and E51
1 = Reset only E50
2 = Reset only E51
4 = Reset all events including E51 except for
E50
Time reading and setting
T
R, W
SS.sss
Date and time reading and setting
D
R, W
YY-MM-DD HH.MM;SS.sss
Type designation of the relay
F
R
REM 610
Unlatching output contacts
V101
W
1 = Unlatch
Clearing targets and memorized values and
unlatching contacts (master reset)
V102
W
1 = Clear and unlatch
FLA secondary (protected unit scaling factor)
V103
R, W (P)
0.50...2.50
96
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537
Summary of Contents for REM 610
Page 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 124: ...124 ...
Page 144: ...144 ...
Page 154: ...154 ...
Page 157: ......