background image

Relion

®

 615 Series

Motor Protection and Control

REM615 ANSI

DNP3 Point List Manual

Summary of Contents for REM615 ANSI

Page 1: ...Relion 615 Series Motor Protection and Control REM615 ANSI DNP3 Point List Manual...

Page 2: ......

Page 3: ...Document ID 1MAC254287 MB Issued 4 14 2011 Revision B Product version 4 0 Copyright 2011 ABB All rights reserved...

Page 4: ...osed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of ABB Group All other brand or product names mentioned in this document may be trademarks or...

Page 5: ...roduct failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipme...

Page 6: ...ive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255 26 for the EMC directive and with the product standards EN 60255 6...

Page 7: ...t 4 Document revision history 5 Related documentation 5 Symbols and conventions 5 Safety indication symbols 5 Manual conventions 6 Functions codes and symbols 7 Section 2 DNP3 data mappings 9 Overview...

Page 8: ...Section 1MAC254287 MB B 2 REM615 ANSI Point List Manual...

Page 9: ...n with the corresponding communication protocol manual 1 2 Intended audience This manual addresses the communication system engineer or system integrator responsible for pre engineering and engineerin...

Page 10: ...tion manual contains instructions on how to operate the IED once it has been commissioned The manual provides instructions for monitoring controlling and setting the IED The manual also describes how...

Page 11: ...be understood that operation of damaged equipment could under certain operational conditions result in degraded process performance leading to personal injury or death Therefore comply fully with all...

Page 12: ...are presented in bold for example Select Main menu Settings LHMI messages are shown in Courier font for example To save the changes in non volatile memory select Yes and press Parameter names are show...

Page 13: ...PS U1 1 Negative sequence overvoltage protection instance 1 NSPTOV1 47 U2 1 Frequency protection instance 1 FRPFRQ1 81 f f df dt 1 Negative sequence overcurrent protection for motors instance 1 MNSPTO...

Page 14: ...ce voltage measurement instance 1 VSMSQI1 V1 V2 V0 U1 U2 U0 Single phase power and energy measurement instance 1 SPEMMU1 SP SE SP SE Three phase power and energy measurement instance 1 PEMMU1 P E P E...

Page 15: ...able 3 Device Physical Information LPHD1 DNP Object Type No Event Point Index DNP Class Enable d Description Scale Factor IEC61850 Data Attribute Name BI 0 Class 1 and 0 Yes Protection LLN0 Settings R...

Page 16: ...O6 stVal BI 156 Class 1 and 0 Yes Led 7 On LD0 LEDGGIO1 SPCSO7 stVal BI 157 Class 1 and 0 Yes Led 8 On LD0 LEDGGIO1 SPCSO8 stVal BI 158 Class 1 and 0 Yes Led 9 On LD0 LEDGGIO1 SPCSO9 stVal BI 159 Clas...

Page 17: ...GGIO130 Ind3 stVal BI 118 Class 1 and 0 Yes X130 Input 4 LD0 XGGIO130 Ind4 stVal BI 119 Class 1 and 0 Yes X130 Input 5 LD0 XGGIO130 Ind5 stVal BI 120 Class 1 and 0 Yes X130 Input 6 LD0 XGGIO130 Ind6 s...

Page 18: ...iption Scale Factor IEC61850 Data Attribute Name BI 100 Class 1 and 0 Yes 51G Trip Operate LD0 EFLPTOC1 Op general BI Yes 101 Class 0 Yes 51G Enable Current Multiplier LD0 EFLPTOC1 InEnaMult stVal DNP...

Page 19: ...es 27PS Positive Sequence Under Voltage 1 LD0 PSPTUV1 Op general DNP Object Type No Event Point Index DNP Class Enabled Description Scale Factor IEC61850 Data Attribute Name BI 261 Class 1 and 0 Yes 4...

Page 20: ...p general DNP Object Type No Event Point Index DNP Class Enabled Description Scale Factor IEC61850 Data Attribute Name BI 329 Class 1 and 0 Yes 46M 2 Negative Sequence Overcurrent Protection For Motor...

Page 21: ...tVal AI 191 Class 2 and 0 Yes 49M Thermal Level 100 LD0 MPTTR1 TmpRl mag f AI Yes 192 Class 0 Yes 49M The Ambient Temperature Used In The Calculation 100 LD0 MPTTR1 TmpUsed mag f AI Yes 193 Class 0 Ye...

Page 22: ...ass 1 and 0 Yes 86 94 1 Master Trip General Output 1 LD0 TRPPTRC1 Tr general BI 8 Class 1 and 0 Yes 86 94 1 Master Trip Operate Input 1 LD0 TRPPTRC1 Op general BI Yes 605 Class 0 Yes 86 94 1 Reset tri...

Page 23: ...292 Class 1 and 0 Yes AFD 3 Fault Arc Detected 3 LD0 ARCSARC31 FADet stVal BI Yes 293 Class 0 Yes AFD 3 Remote Fault Arc Detected 3 LD0 ARCSARC31 InRemFA stVa l DNP Object Type No Event Point Index D...

Page 24: ...NP Class Enabled Description Scale Factor IEC61850 Data Attribute Name BI 630 Class 1 and 0 Yes 52 Breaker Block Open CTRL CBXCBR1 BlkOpn stVal BI 631 Class 1 and 0 Yes 52 Breaker Block Close CTRL CBX...

Page 25: ...xceeded Alarm Limit 1 LD0 SSCBR1 APwrAlm stVal BI 33 Class 1 and 0 Yes 52CM Accumulated Currents Power Iyt Exceeded Lockout Limit 1 LD0 SSCBR1 APwrLO stVal BI 34 Class 1 and 0 Yes 52CM Remaining Life...

Page 26: ...e Name BI 297 Class 1 and 0 Yes CCM Current Circuit Supervision Trip Operate LD0 CCRDIF1 Op general BI 298 Class 1 and 0 Yes CCM Current Circuit Supervision Alarm LD0 CCRDIF1 Alm stVal DNP Object Type...

Page 27: ...LD0 CMMXU1 A phsC cVal mag f DNP Object Type No Event Point Index DNP Class Enabled Description Scale Factor IEC61850 Data Attribute Name BI Yes 165 Class 0 Yes IA IB IC 1 Reset Max Demands LD0 CMSTA1...

Page 28: ...and 100 LD0 CMSTA2 MaxAmpsA mag f AI Yes 62 Class 0 Yes IA IB IC 2 Phase B Average Demand 100 LD0 CMSTA2 AvAmpsB mag f AI Yes 63 Class 0 Yes IA IB IC 2 Phase B Maximum Demand 100 LD0 CMSTA2 MaxAmpsB m...

Page 29: ...Class 1 and 0 Yes IG High Warning LD0 RESCMMXU1 HiWrn stVal AI 66 Class 2 and 0 Yes IG Magnitude RMS 100 LD0 RESCMMXU1 A res instCVal mag f AI 67 Class 2 and 0 Yes IG Magnitude deadbanded 100 LD0 RES...

Page 30: ...CVal mag f AI 103 Class 2 and 0 Yes V1 V2 V0 Zero Sequence Mag Deadband 100 LD0 VSMSQI1 SeqV c3 cVal mag f DNP Object Type No Event Point Index DNP Class Enabled Description Scale Factor IEC61850 Data...

Page 31: ...PEMMXU1 TotVAr instMag f AI 113 Class 2 and 0 Yes P E Total Apparent Power 1 1 LD0 PEMMXU1 TotVA instMag f AI 114 Class 2 and 0 Yes P E Average Power Factor 1 100 LD0 PEMMXU1 TotPF instMag f DNP Obje...

Page 32: ...Output 1 LD0 PTGAPC1 Q1 stVal BI Yes 518 Class 0 Yes PT 1 Generic Pulse Timer 1 Output 2 LD0 PTGAPC1 Q2 stVal BI Yes 519 Class 0 Yes PT 1 Generic Pulse Timer 1 Output 3 LD0 PTGAPC1 Q3 stVal BI Yes 520...

Page 33: ...Description Scale Factor IEC61850 Data Attribute Name DNP Object Type No Event Point Index DNP Class Enabled Description Scale Factor IEC61850 Data Attribute Name BI Yes 475 Class 0 Yes TOF 1 Generic...

Page 34: ...LD0 TOFGAPC2 In2 stVal BI Yes 495 Class 0 Yes TOF 2 Generic Time Delay Off 2 Input 3 LD0 TOFGAPC2 In3 stVal BI Yes 496 Class 0 Yes TOF 2 Generic Time Delay Off 2 Input 4 LD0 TOFGAPC2 In4 stVal BI Yes...

Page 35: ...8 LD0 TONGAPC1 In8 stVal BI Yes 450 Class 0 Yes TON 1 Generic Time Delay On 1 Output 1 LD0 TONGAPC1 Q1 stVal BI Yes 451 Class 0 Yes TON 1 Generic Time Delay On 1 Output 2 LD0 TONGAPC1 Q2 stVal BI Yes...

Page 36: ...scription Scale Factor IEC61850 Data Attribute Name DNP Object Type No Event Point Index DNP Class Enabled Description Scale Factor IEC61850 Data Attribute Name BI Yes 407 Class 0 Yes SR 1 Set Reset F...

Page 37: ...0 Yes SR 2 Set 3 Set Reset Flip Flop 2 LD0 SRGAPC2 Set3 stVal BI Yes 436 Class 0 Yes SR 2 Set 4 Set Reset Flip Flop 2 LD0 SRGAPC2 Set4 stVal BI Yes 437 Class 0 Yes SR 2 Set 5 Set Reset Flip Flop 2 LD0...

Page 38: ...cRs stVal AI 116 Class 2 and 0 Yes Fault Record Operation Counter 1 LD0 FLTMSTA1 OpCnt stVal AI 117 Class 2 and 0 Yes Last Fault Max Start Duration Of All Stages During The Fault 1 LD0 FLTMSTA1 StrDur...

Page 39: ...ent b 100 LD0 FLTMSTA1 MaxAmpsCb mag f AI 146 Class 2 and 0 Yes Maximum residual current b 100 LD0 FLTMSTA1 MaxAmpsNb mag f AI 147 Class 2 and 0 Yes Phase A current b 100 LD0 FLTMSTA1 AmpsAb mag f AI...

Page 40: ...172 Class 2 and 0 Yes Positive sequence voltage b 100 LD0 FLTMSTA1 VPsSeqb mag f AI 173 Class 2 and 0 Yes Negative sequence voltage b 100 LD0 FLTMSTA1 VNgSeqb mag f AI 175 Class 2 and 0 Yes Last Fault...

Page 41: ...haTm Oper ctl Val BO 9 Yes X130 Output 1 LD0 XGGIO130 SPCSO1 Oper ctlVal BO 10 Yes X130 Output 2 LD0 XGGIO130 SPCSO2 Oper ctlVal BO 11 Yes X130 Output 3 LD0 XGGIO130 SPCSO3 Oper ctlVal BO 12 Yes X110...

Page 42: ...al BO 47 Yes SP SE Reset of accumulated energy readings LD0 SPEMMTR1 SupDmdRs Oper ct lVal BO 49 Yes 52 Recloser 1 Switch Control CTRL CBCSWI1 Pos Oper ctlVal BO 51 Yes DFR Trig Recording DR RDRE1 Rcd...

Page 43: ...document in the standard format defined in the DNP3 Subset Definitions Document While it is referred to in the DNP3 Subset Definitions as a document it is in fact a table and only a component of a to...

Page 44: ...2048 Maximum data link re tries Maximum application layer re tries None None Fixed Configurable Configurable 0 65535 Requires data link layer confirmation Never Always Sometimes Configurable as Never...

Page 45: ...is hardware error 4 All other control points may be controlled by either direct or SBO controls Reports binary input change events when no specific variation requested Reports time tagged binary input...

Page 46: ...Yes No Max number of files open 0 Selected Not selected DNP3 device profile document OBJECT REQUEST Library will parse RESPONSE Library will respond with Object number Variation number Description Fun...

Page 47: ...01 start stop 17 28 index 30 2 default 16 bit analog input 1 read 00 01 start stop 06 no range or all 07 08 limited qty 17 28 index 129 response 00 01 start stop 17 28 index 30 3 32 bit analog input w...

Page 48: ...2 Class 1 data 1 read 06 no range or all 20 enbl unsol 21 dab unsol 22 assign class 07 08 limited qty 06 no range or all 60 3 Class 2 data 1 read 06 no range or all 07 08 limited qty 20 enbl unsol 21...

Page 49: ...h qualifiers 17 or 28 respectively Other wise static object requests sent with qualifiers 00 01 06 07 or 08 will be responded with qualifiers 00 or 01 For change event objects qualifiers 17 or 28 are...

Page 50: ...Section 3 1MAC254287 MB B DNP3 protocol implementation 44 REM615 ANSI Point List Manual...

Page 51: ...TRL Control logical device DFR Digital fault recorder DNP3 A distributed network protocol originally developed by Westronic The DNP3 Users Group has the ownership of the protocol and assumes responsib...

Page 52: ...Section 4 1MAC254287 MB B Glossary 46 REM615 ANSI Point List Manual Val Value...

Page 53: ......

Page 54: ...stribution Automation 4300 Coral Ridge Drive Coral Springs FL 33065 USA Phone 1 800 523 2620 Phone 1 954 752 6700 Fax 1 954 345 5329 www abb com substationautomation 1MAC254287 MB B Copyright 2011 ABB...