152
Intercircuit bridging protection (TOVI)
&KDSWHU
9ROWDJH
)LJXUH ,QWHUFLUFXLWEULGJLQJSURWHFWLRQIXQFWLRQVLPSOLILHGORJLFGLDJUDP
The output operates if the voltage becomes higher than the set operate value U> under
a time exceeding the set definite time delay t.
An external signal connected to the input TOVI-BLOCK may block the function.
&DOFXODWLRQV
The parameters for the intercircuit bridging protection function are set via the local
HMI or PST (Parameter Setting Tool). Refer to the Technical reference manual for set-
ting parameters and path in local HMI.
If set frequency is 50 Hz then the operate voltage (U4) must be set higher than the high-
est permitted 16 2/3 Hz voltage on the line. If set frequency is 16 2/3 Hz then the operate
voltage (U1) must be set higher than the highest permitted 50 Hz voltage on the line. A
safety margin of at least 10 % in addition to the inaccuracies of the voltage transformer
and the measuring function is recommended.
TOVI-BLOCK
U
U>
&
t
TOVI-TRIP
xx01000092.vsd
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...