228
Apparatus control
&KDSWHU
&RQWURO
also use the solution in figure 108 if the close command from the synchrocheck relay is
connected via a binary input to the SY_OK input on SWICONA. Alternative 3 in figure
111 shows the connection to an external synchronization equipment, for example, type
RES 010.
For the external synchronization relay, the close command is normally handled outside
the control terminal. At the close command from the operator, COMCON activates the
EXECUTE output and SWICONB the SEL_CLOS and EXE_CLOS outputs. SWI-
CONB has two inputs SY_RUN and SY_FAIL, which need the status information of
the synchronization sequence. The SY_RUN signal can be connected from the synchro-
nization relay, so it will be activated when the synchronization relay is in progress and
waiting for its close command.
The feedback signal of the close command in the figures 109 and 110 is used to start
the supervision timer T_START, which supervises the movement of the drive, that is,
the position change from open (01) -> 00.
)LJXUH&RQQHFWLRQH[DPSOHIRUH[WHUQDOV\QFKURFKHFNHTXLSPHQWDQGWKHDSSDUD
WXVFRQWUROPRGXOHVDOWHUQDWLYH
99000341.vsd
COMCON
CLOSE
EXECUTE
&
&
SWICONB
CLOSE
EXECUTE
SEL_CLOS
SY_RUN
SY_FAIL
Timer
INPUT
ON
SYNCH
CLOSE
U1
U2
+
-
CB
close
coil
External synchrocheck
or synchronization
equipment
BI/BO
+
&
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...