295
LED indication function (HL, HLED)
&KDSWHU
0RQLWRULQJ
5HVWDUWLQJPRGH
In the re-starting mode of operation each new start resets all previous active LEDs and
activates only those which appear during one disturbance. Only LEDs defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S) will initiate a reset and
a restart at a new disturbance. A disturbance is defined to end a settable time after the
reset of the activated input signals or when the maximum time limit has been elapsed.
$FNQRZOHGJPHQWUHVHW
)U0,
The active indications can be acknowledged/reset manually. Manual acknowledgment
and manual reset have the same meaning and is a common signal for all the operating
sequences and LEDs. The function is positive edge triggered, not level triggered. The
acknowledgment/reset is performed via the C-button on the Local HMI according to the
sequence in figure 162.