21
Terminal identification and base values
&KDSWHU
*HQHUDO
The relay setting value IP>> is given in percentage of the secondary base current value,
Ixb, associated to the current transformer input Ix:
(Equation 11)
The value of Ixb can be calculated as:
(Equation 12)
The voltage transformer secondary setting voltage (Us
SEC
) is:
(Equation 13)
The relay setting value UPE< is given in percentage of the base voltage value, Uxb, as-
sociated to the voltage transformer input Ux:
where:
I
SEC
= secondary rated current of the main CT
I
PRIM
= primary rated current of the main CT
Is
= primary setting value of the current
where:
U
SEC
secondary rated voltage of the main VT
U
PRIM
primary rated voltage of the main VT
Us
primary setting value of the voltage
IP>>
Is
SEC
Ixb
--------------
100
⋅
=
Ixb
Rated primary current
CT ratio
----------------------------------------------------------
=
Us
SEC
U
SEC
U
PRIM
----------------
Us
⋅
=