380
Optical fibre communication module
&KDSWHU
'DWDFRPPXQLFDWLRQ
)LJXUH0XOWLSOH[HGOLQNILEUHRSWLFDOJDOYDQLFFRQQHFWLRQZLWK)2;3OXV
'HVLJQ
The optical communication module is designed to work with both 9/125
µ
m single-
mode fibres and 50/125 or 62,5/125
µ
m multimode fibres at 1300 nm wavelength. The
connectors are of type FC-PC (SM) or FC (MM) respectively. Two different levels of
optical output power are used. The level of optical power is selected with a setting. Low
power is used at short fibers in order not to saturate the receiver and thereby jeopardiz-
ing the functionality, and high power is used for long fibers to handle the high attenua-
tion that follow. The optical budget of the modem, at high output power, is 16dB for
single mode fiber and 21dB for multi mode fiber. This means that the total loss in the
fiber has to be less than the optical budget. The losses in the connection to the protection
terminal are not to be included in the optical budget since they are already accounted
for. The maximum reach will depend on the properties of the used optical fiber but be
around 20 km for multi mode fibers and about 30 km for single mode during normal
conditions.
Example: The attenuation in the fibres is normally approximately 0.8 dB/km for multi-
mode and 0.4 dB/km for single-mode. Additional attenuation due to installation can be
estimated to be 0.2dB/km for multimode and 0.1 dB/km for single-mode fibres. For sin-
gle-mode fibre and high output power this results in a maximum distance of 32km. With
lower attenuation, a longer distance can be achieved.
xx00000535.vsd
FOX 6
Plus
REx5xx
Optical
fibres
MUX
Galvanic
G.703
other
users
to the
other end
<10 m
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...