3 zone impedance protection (Z(n)RW)
&KDSWHU
/LQHLPSHGDQFH
The limitation in the reactive reach is a straight line, parallel with the R-axis. The lim-
itation in the resistive reach is two straight parallel lines with a small incline (9°) to-
wards the X-axis crossing the R-axis at +/-RF.The setting value of the resistive and re-
active reach determines whether the resistive directional line in the second quadrant in-
fluences the characteristic or not.
The directional line forms an angle of 25° towards the X-axis in the second quadrant.
In the fourth quadrant the angle (ArgDir) can be set to 15°, 30° or 45° towards the R-
axis in order to adapt the setting to series compensated lines. ArgDir is valid for all
zones.
An extra directional line (ArgLd) can be placed in the first quadrant for zones two and
three to reduce load encroachment problems. The angle for this can be set to 15°, 30°
or 45° towards the R-axis. If ArgLd is set the directional line in the fourth quadrant ap-
plies only zone 1.
The direction for each zone can be programmed. In figure 30, a typical example of char-
acteristics for non-directional, reverse and forward directed impedance measuring
zones are shown. The set value of a reach in the resistive direction determines whether
the directional line in the second quadrant meets the reactive or the resistive blinder.
The values for the reach in the reactive and resistive direction for a particular zone are
the same for forward and reverse impedance measuring elements and for the non-direc-
tional mode of operation.
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...