7.10.2
Limit counter L4UFCNT
GUID-E35C0EBD-081E-4EC2-9DE9-D276DBA8354A v1
The Limit counter function L4UFCNT can be tested by connecting a binary input to the counter
and applying pulses to the counter. The speed of the pulses must not exceed the cycle time of
the function. Normally the counter will be tested when testing the function that the counter is
connected to, such as the trip function. When the function is configured, test it together with
the function that operates it. Trig the function and check that the counter result corresponds
to the number of operations.
7.10.2.1
Completing the test
GUID-8E1A0F3F-0611-4AF4-9FE4-63E750AE90C3 v1
Continue to test another function or end the test by changing the Test mode setting to
Off.
Restore connections and settings to their original values, if they were changed for testing
purposes.
7.11
Testing metering functions
7.11.1
Pulse counter PCGGIO
M13405-2 v6
The test of the Pulse counter function PCGGIO requires the Parameter Setting tool in PCM600
or an appropriate connection to the local HMI with the necessary functionality. A known
number of pulses with different frequencies are connected to the pulse counter input. The test
should be performed with settings
Operation = On or Operation = Off and the function
blocked or unblocked. The pulse counter value is then checked in PCM600 or on the local HMI.
7.12
Testing station communication
7.12.1
Establishing connection and verifying the IEC 61850
communication
GUID-0EEBE65F-5A84-4D2E-A358-BF5283E948D6 v1
About this chapter
This chapter contains instructions on how to establish connection and verify that the IEC
61850 communication operates as intended, when the IED is connected to an Ethernet
network via the optical ports of the COM module.
7.12.1.1
Overview
GUID-F8AA9CC0-E9DC-4656-B209-879B18243189 v1
The COM03 ports are used for substation bus (IEC 61850-8-1) communication as well as
redundant communication.
The COM05 ports are also used for communication but not redundant communication.
For IEC 61850-8-1 redundant communication according to IEC62439–3 Edition 2, port LAN_1A
and LAN_1B is utilized.
Redundant communication according to IEC62439–3 Edition 1 and IEC 61850–
9–2LE process bus communication are not supported in the 650 Ver 1.3 series
IEDs.
Section 7
1MRK 505 293-UEN B
Testing functionality
96
Breaker protection REQ650
Commissioning manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for REQ650 1.3 IEC
Page 1: ...Relion 650 SERIES Breaker protection REQ650 Version 1 3 IEC Commissioning manual ...
Page 2: ......
Page 12: ...6 ...
Page 20: ...14 ...
Page 28: ...22 ...
Page 40: ...34 ...
Page 42: ...36 ...
Page 116: ...110 ...
Page 123: ...117 ...