Set value:
Mode
Formula used for complex power calculation
L1L2
*
*
1 2
1
2
(
)
L L
L
L
S
U
I
I
=
×
-
EQUATION1700 V1 EN-US
(Equation 7)
L2L3
*
*
2 3
2
3
(
)
L L
L
L
S
U
I
I
=
×
-
EQUATION1701 V1 EN-US
(Equation 8)
L3L1
*
*
3 1
3
1
(
)
L L
L
L
S
U
I
I
=
×
-
EQUATION1702 V1 EN-US
(Equation 9)
L1
*
1
1
3
L
L
S
U
I
= ×
×
EQUATION1703 V1 EN-US
(Equation 10)
L2
*
2
2
3
L
L
S
U
I
= ×
×
EQUATION1704 V1 EN-US
(Equation 11)
L3
*
3
3
3
L
L
S
U
I
= ×
×
EQUATION1705 V1 EN-US
(Equation 12)
2.
Adjust the injected current and voltage to the set values in % of
IBase and UBase
(converted to secondary current and voltage). The angle between the injected current
and voltage shall be set equal to the set direction
Angle1, angle for stage 1 (equal to 0° for
low forward power protection and equal to 180° for reverse power protection). Check
that the monitored active power is equal to 100% of rated power and that the reactive
power is equal to 0% of rated power.
3.
Change the angle between the injected current and voltage to
90°. Check that
the monitored active power is equal to 0% of rated power and that the reactive power is
equal to 100% of rated power.
4.
Change the angle between the injected current and voltage back to 0°. Decrease the
current slowly until the START1 signal, start of stage 1, is activated.
5.
Increase the current to 100% of
IBase.
6.
Switch the current off and measure the time for activation of TRIP1, trip of stage 1.
7.
If a second stage is used, repeat steps
7.3.14.2
Completing the test
SEMOD175027-15 v4
Continue to test another function or end the testing by setting the parameter
TestMode to Off
under Main menu/Tests/IED test mode/TESTMODE:1. If another function is tested, then set
the parameter
Blocked to No under Main menu/Tests/Function test modes/Current/
GUPPDUP(37,P<)/GUPPDUP:1 for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter
Blocked to Yes, for each individual function that
has been tested.
7.3.15
Directional overpower protection GOPPDOP
SEMOD175058-3 v5.1.1
Prepare the IED for verification of settings as outlined in section
.
Values of the logical signals for GOPPDOP are available on the local HMI under Main menu/
Tests/Function status/Current/GOPPDOP(32,P>)/GOPPDOP:X. The Signal Monitoring in
PCM600 shows the same signals that are available on the local HMI.
Section 7
1MRK 505 293-UEN B
Testing functionality
64
Breaker protection REQ650
Commissioning manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for REQ650 1.3 IEC
Page 1: ...Relion 650 SERIES Breaker protection REQ650 Version 1 3 IEC Commissioning manual ...
Page 2: ......
Page 12: ...6 ...
Page 20: ...14 ...
Page 28: ...22 ...
Page 40: ...34 ...
Page 42: ...36 ...
Page 116: ...110 ...
Page 123: ...117 ...