88
1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
The alarm channels are seen as function blocks in the transformer terminal
configuration:
5.1.16.1.
Non-latched alarm
In a non-latched mode, the ON signal switches between ON and OFF state texts and
the corresponding LED colors. Alarm acknowledgement (ACK) clears the last time
stamp line of the alarm view, but leaves the corresponding alarm LED state
unchanged. An event is generated on the rising and falling edge of the ON signal and
by acknowledgement.
Alarind4_b
Alarind5_b
Fig. 5.1.16.1.-1 Example of a non-latched alarm
5.1.16.2.
Latched alarm, steady LED
Latched, steady alarms can be acknowledged only when the ON signal is inactive.
The time stamp of the first alarm is recorded. Successful acknowledgement clears
the time stamp line of the alarm view and the corresponding alarm LED. An event
is generated on the rising and falling edge of the ON signal and by
acknowledgement.
Alarm channel
Function block
Alarm channel 1
MMIALARM1
Alarm channel 2
MMIALARM2
Alarm channel 3
MMIALARM3
Alarm channel 4
MMIALARM4
Alarm channel 5
MMIALARM5
Alarm channel 6
MMIALARM6
Alarm channel 7
MMIALARM7
Alarm channel 8
MMIALARM8
Non-latched, steady (example 1)
On text
09-24 12:40:00
On colour for steady LED
Off text
Off colour for steady LED
On text
09-24 12:40:00
On colour for steady LED
Off text
09-24 12:40:00
Off colour for steady LED
On text
On colour for steady LED
ALARM
ON
ACK
Non-latched, steady (example 1 continues)
On text
On colour for steady LED
Off text
09-24 12:40:00
Off colour for steady LED
ACK
ON
ALARM
Off text
Off colour for steady LED