17. Technical data
Table 6. Dimensions
Description
Value
Width
frame
177 mm
case
164 mm
Height
frame
177 mm (4U)
case
160 mm
Depth
201 mm (153 + 48 mm)
Weight
complete IED
4.1 kg
plug-in unit only
2.1 kg
Table 7. Power supply
Description
Type 1
Type 2
U
aux
nominal
100, 110, 120, 220, 240 V AC, 50 and
60 Hz
24, 30, 48, 60 V DC
48, 60, 110, 125, 220, 250 V DC
Maximum interruption time in the
auxiliary DC voltage without
resetting the IED
50 ms at U
n
rated
U
aux
variation
38...110% of U
n
(38...264 V AC)
50...120% of U
n
(12...72 V DC)
80...120% of U
n
(38.4...300 V DC)
Start-up threshold
19.2 V DC (24 V DC * 80%)
Burden of auxiliary voltage supply
under quiescent (P
q
)/operating
condition
DC < 12.0 W (nominal)/< 18.0 W (max)
AC< 16.0 W (nominal)/< 21.0W (max)
DC < 12.0 W (nominal)/< 18.0 W (max)
Ripple in the DC auxiliary voltage
Max 15% of the DC value (at frequency of 100 Hz)
Fuse type
T4A/250 V
Transformer Protection and Control
1MRS756891 F
RET615
Product version: 4.0
ABB
25
Summary of Contents for RET615
Page 1: ...Relion 615 series Transformer Protection and Control RET615 Product Guide...
Page 65: ...65...
Page 66: ......
Page 67: ......