1MRS750886-MUM
17
REU 513
User’s Guide
ABB Substation Automation
Products and Systems
2.1.3.
Protection
2.1.3.1.
Block diagram
Fig. 2.1.3.1.-1 Block diagram of the combined overvoltage and undervoltage
relay REU 513
2.1.3.2.
Overvoltage unit
When one or several of the measured voltages exceed the set start value of the low-
set stage U> and the preset start time of ~ 60 ms elapses, the overvoltage unit begins
delivering a start signal. Further, when the set operate time for the low-set stage at
definite-time operation or the calculated operate time at inverse-time operation
passes, the overvoltage unit operates.
In the same way as the low-set stage, the high-set stage U>> of the overvoltage unit
begins delivering a start signal after a preset ~ 50 ms start time when the set start
value is exceeded. When the set operate time for the high-set stage at definite-time
operation or the calculated operate time at inverse-time operation elapses, the
overvoltage unit operates.
SGR2/x
SGR1/x
SO2
1
1
SGR7/x
SGR8/x
SGR6/x
SGR5/x
U<<
t<<, k<<
U>
U>>
U<
U<<
t>
t>>
t<
t<<
1
4
60 ms
50 ms
SO1
2
3
SGF2/5
SGF2/2
SGB1/4
SGB1/6
BI
SGB1/5
SGB1/8
SGB1/1
SGB1/2
SGB1/3
SGR3/x
SGR4/x
U>>
t>>, k>>
50 ms
SGF2/6
SGF4/3...4
SGF2/7
t<, k<
PO2
SGF1/2
40/80 ms
SGF1/5
PO1
SGF1/1
1
SGB1/7
U
U
U
U>
t>, k>
SGF4/1...2
U<
80 ms
SGF4/5
SGF1/3
40/80 ms
40/80 ms
5 s
1
1
0.1 ... 1s
SGF1/4
5 s
40/80 ms
C
START
SGF3/1, 3, 5,7
TRIP
SGF3/2, 4, 6, 8
SGF2/4
&
&
U1s
BlockU5_3
RESET INDICATORS, LATCHED OUTPUT RELAYS AND REGISTERS
RESET INDICATORS AND LATCHED OUTPUT RELAYS
RESET INDICATORS
SETTINGS (Group 1 / Group 2)
12
23
31
0.20 Un
0.20 Un
C
C
SGF4/6
C