Recorded data
Parameter V1 indicates the highest and parameter V2 the lowest voltage value
measured as multiples of the rated voltage U
n
since the last reset. Parameter V3
shows the average voltage value during one minute’s time, updated once a minute.
The average voltage during a ten minutes’ period is shown by parameter V4. The
value is updated for the first time ten minutes after the relay start-up and after that
once a minute. Parameters V5...V8 indicate the number of starts of the protection
stages, parameter V9 shows the operation indication code and parameter V10 the
stage that has tripped.
Table 21: Recorded data: Parameters V1…V10
Recorded data
Para-
meter
R/W
Value
Maximum voltage measured after reset
V1
R
0...2 x U
n
Minimum voltage measured after reset
V2
R
0...2 x U
n
Average voltage during 1 minute
V3
R
0...2 x U
n
Average voltage during 10 minutes
V4
R
0...2 x U
n
Number of starts of stage U>
V5
R
0...255
Number of starts of stage U>>
V6
R
0...255
Number of starts of stage U<
V7
R
0...255
Number of starts of stage U<<
V8
R
0...255
Operation indication code
V9
R
0 = ---
1 = starting of stage U>
2 = tripping of stage t>
3 = starting of stage U>>
4 = tripping of stage t>>
5 = starting of stage U<
6 = tripping of stage t<
7 = starting of stage U<<
8 = tripping of stage t<<
9 = tripping of CBFP unit
Stage/voltage that caused tripping;
the value may also be a combination of
two or more of the individual values,
e.g. 24 (= 8 + 16)
V10
R
1 = U
12
>
2 = U
23
>
4 = U
31
>
8 = U
12
>>
16 = U
23
>>
32 = U
31
>>
64 = U
12
<
128 = U
23
<
256 = U
31
<
512 = U
12
<<
1024 = U
23
<<
2048 = U
31
<<
4096 = U1s