ABB Substation Automation
Products and Systems
User’s Guide
REU 513
52
1MRS750886-MUM
2.2.2.
Technical data
Table 36: Dimensions
• Width 111.4 mm
• Height, frame 265.9 mm (6U), box 255.8 mm
• Depth 235 mm (245.1 mm with a protective rear cover, available as an option)
• Enclosure size 1/4 (x 19”)
• Weight of the relay ~3.1 kg
Table 37: Power supply
U
r
=110/120/220/240 V ac
U
r
=48/60/110/125/220 V dc
• Operating range
80…265 V ac
38…265 V dc
• Relay power start-up time, typical
300 ms
• Burden of auxiliary supply under quiescent/
operating condition
~ 4 W/~10 W
• Ripple in dc auxiliary voltage
Max 12% of the dc value
• Interruption time in auxiliary dc voltage without
resetting
< 30 ms at 48 V dc
< 100 ms at 110 V dc
< 500 ms at 220 V dc
Table 38: Energizing inputs
Rated frequency
50/60 Hz
±
5 Hz
Rated voltage U
n
100/110/115/120 V
Maximum input voltage
• continuously
2 x U
n
• for 10 s
3 x U
n
Power consumption at U
n
< 0.5 VA