ABB Substation Automation
Products and Systems
User’s Guide
REU 513
48
1MRS750886-MUM
Input and output signals
The measured voltages and the status of the binary input signal can be read (R) with
parameters I1...I4. When the value of parameter I4 is 1, the binary input is energized.
The value of the calculated positive-phase-sequence voltage can be read via
parameter I5.
Each protection stage has its internal output signal. These signals can be read (R)
with parameters O1...O8. The state of the output contacts can be read (R) or changed
(W) with parameters O9...O12. When any of the values of parameters O1...O12
changes from 0 to 1, it is recorded in the corresponding parameter of O21...O32. The
values recorded can be read via these parameters and they remain stored until reset.
Table 28: Inputs
Description
Parameters (R)
Value
Voltage U
12
I1
0...2 x U
n
Voltage U
23
I2
0...2 x U
n
Voltage U
31
I3
0...2 x U
n
Binary input signal BI
I4
0 or 1
Positive-phase-sequence voltage
I5
0...2 x U
n
Table 29: Output signals
Status of the protection stages
State of stage
(R)
Recorded
functions (R)
Value
Starting of stage U>
O1
O21
0 or 1
Tripping of stage U>
O2
O22
0 or 1
Starting of stage U>>
O3
O23
0 or 1
Tripping of stage U>>
O4
O24
0 or 1
Starting of stage U<
O5
O25
0 or 1
Tripping of stage U<
O6
O26
0 or 1
Starting of stage U<<
O7
O27
0 or 1
Tripping of stage U<<
O8
O28
0 or 1