Table 5.1.17.-10 Outputs
Operation of
output contact
State of output (R,
W, P), channel 0
Recorded
functions (R),
channel 0
Value
Output PO1
O41
O101
0/1
Output PO2
O42
O102
0/1
Output PO3
a)
O43
O103
0/1
b)
Output SO1
O44
O104
0/1
Output SO2
O45
O105
0/1
Output PO3 (trip
lockout)
c)
O46
-
0/1
b)
Output SO3
O47
O107
0/1
d)
Output SO4
O48
O108
0/1
d)
Output SO5
O49
O109
0/1
d)
Enabling activation
of output contacts
PO1, PO2, PO3,
SO1, SO2, SO3,
SO4 and SO5 via
the SPA bus
O51
-
0/1
a)
State of output when the trip lockout function is not in use.
b)
Either O43/O103 or O46 is to be used at a time.
c)
State of output when the trip lockout function is in use.
d)
If the optional I/O module has not been installed, a
“
9
”
is shown when the parameter is read via
the SPA bus.
Parameters
O41
...
O49
and
O51
control the physical output
contacts which can be connected to circuit breakers, for instance.
Parameters for IEC 60870-5-103 remote communication
protocol
Table 5.1.17.-11 Settings
Description
Parameter
(channel 507)
R, W, P
Value
Unit address of the relay
507V200
R, W
1...254
Data transfer rate
(IEC 60870-5-103), kbps
507V201
R, W
9.6/4.8
100
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version
1MRS755972