103
Table 5.1.17.-13 Settings (Continued)
Description
SPA
parameter
(channel
503)
R, W
Value range
Default Explanation
Class 3 event count
503V23
R, W
0...255
1
Unsolicited reporting
mode
503V24
R, W
0 = UR disabled
1 = immediate
2 = empty UR
3 = empty UR
and enable UR
0
Refer to Unsolicited reporting start up
in Section 5.1.16.5. REU 610-specific
DNP features.
Scaling factor 1
503V101
R, W
0...4294967295
1
Scaling factor 2
503V102
R, W
0...4294967295
1
Scaling factor 3
503V103
R, W
0...4294967295
1
Scaling factor 4
503V104
R, W
0...4294967295
1
Scaling factor 5
503V105
R, W
0...4294967295
1
Baud rate
503V211
R, W
4.8/9.6/19.2/38.4
9.6
Number of stop bits
503V212
R, W
1...2
1
Parity
503V230
R, W
0 = no parity
1 = odd
2 = even
0
Silent interval
503V232
R, W
0...65535 ms
20
Time slot width
503V233
R, W
0...255 ms
10
Number of time slots
503V234
R, W
0...255
8
Collision detection
enabled
503V235
R, W
0 = disabled
1 = enabled
0
DNP module warning
register
503V168
R
Bit coded
0 = OK
DNP module status
register
503V169
R
Bit coded
0 = OK
1MRS755972