125
Table 5.2.3.-6
Signal output SO1 and optional SO4 and SO5
(Continued)
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
(5 A/3 A/1 A for series
connection of SO4 and SO5)
Minimum contact load
100 mA at 24 V AC/DC
Table 5.2.3.-7
Signal output SO2, optional SO3, and IRF output
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
10 A
Make and carry for 0.5 s
15 A
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Table 5.2.3.-8
Power outputs (PO1, PO2, PO3)
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC (PO1 with
both contacts connected in series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
TCS:
-Control voltage range
20...265 V AC/DC
-Current drain through the supervision circuit
~
1.5 mA
-Minimum voltage over a contact
20 V AC/DC (15...20 V)
Table 5.2.3.-9
Enclosure class of the flush-mounted relay
Front side
IP 54
Rear side, top of the relay
IP 40
Rear side, connection terminals
IP 20
Table 5.2.3.-10 Environmental tests and conditions
Recommended service temperature range
(continuous)
-10...+55
°
C
Limit temperature range (short-term)
-40...+70
°
C
Transport and storage temperature range
-40...+85
°
C according to
IEC 60068-2-48
1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
REU 610