131
7.
Check lists
Table 7.-1
Setting group 1
Variable
Group/
Channel 1
(R, P)
Setting range
Default
setting
Custo-
mer's
setting
Pickup value of element 59P-
1
1S1
0.6
…
1.4
×
U
n
(VT)
1.2
×
U
n
(VT)
Operate time of element
59P-1
1S2
0.06
…
600 s
0.06 s
IDMT operation mode setting
for element 59P-1
1S3
0
…
2
0
IDMT time dial 59P-1 TD
1S4
0.05
…
2.00
0.05
Resetting time of element
59P-1
1S5
0.07...60.0 s
0.07 s
Drop-off/pick-up ratio 59P-1
D/P
1S6
0.95
…
0.99
0.97
U
1
/U
2
mode setting of
elements 59P-2 and 27P-2
1S7
0...2
0
Pickup value of element 59P-
2
1S8
0.80
…
1.60
×
U
n
(VT)
1.20
×
U
n
(VT)
Pickup value of element 47
1S9
0.05
…
1.00
×
U
n
(VT)
0.05
×
U
n
(VT)
Operate time of element
59P-2
1S10
0.05
…
600 s
0.05 s
IDMT operation mode setting
for element 59P-2
1S11
0
…
2
0
IDMT time dial 59P-2 TD
1S12
0.05
…
2.00
0.05
Pickup value of element 27P-
1
1S13
0.20
…
1.20
×
U
n
(VT)
0.20
×
U
n
(VT)
Operate time of element
27P-1
1S14
0.10
…
600 s
0.10 s
IDMT operation mode setting
for element 27P-1
1S15
0
…
1
0
IDMT time dial 27P-1 TD
1S16
0.10
…
2.00
0.10
Resetting time of element
27P-1
1S17
0.07...60.0 s
0.07 s
Drop-off/pick-up ratio 27P-1
D/P
1S18
1.01
…
1.05
1.03
Pickup value of element 27P-
2
1S19
0.20
…
1.20
×
U
n
(VT)
0.20
×
U
n
(VT)
Pickup value of element 27D
1S20
0.20
…
1.20
×
U
n
(VT)
0.20
×
U
n
(VT)
Operate time of element
27P-2
1S21
0.10
…
600 s
0.10 s
IDMT operation mode setting
for element 27P-2
1S22
0
…
1
0
IDMT time dial 27P-2 TD
1S23
0.10
…
2.00
0.10
1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
REU 610
Summary of Contents for REU 610
Page 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 10: ...10 ...
Page 128: ...128 ...
Page 138: ......
Page 139: ......